Table L. Output/Inverter Section Customer Interface Inputs and Outputs
CUSTJ4
Terminal
1
2
3
4
5
6
7
8
9
10
CUSTJ2
Terminal
1
2
3
4
5
6
7
8
9
10
CUSTTB
Terminal
1
2
3
4
5
6
7
8
9
10
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101
Name
BLDG ALARM 1
BLDG ALARM 1 RTN
BLDG ALARM 2
BLDG ALARM 2 RTN
BLDG ALARM 3
BLDG ALARM 3 RTN
BLDG ALARM 4
BLDG ALARM 4 RTN
NOT USED
NOT USED
RELAY 1 NC
RELAY RTN
RELAY 1 NO
NOT USED
NOT USED
RELAY 2 NC
RELAY RTN
RELAY 2 NO
NOT USED
NOT USED
CB3---AUX #2
CB3---AUX #2
NOT USED
REMOTE TO BYPASS
REMOTE TO BYPASS
REMOTE TO UPS
REMOTE TO UPS
NOT USED
REMOTE EPO
REMOTE EPO RTN
Description
Programmable UPS alarm. Activated by a remote
Programmable UPS alarm. Activated by a remote
dry contact closure.
Programmable UPS alarm. Activated by a remote
Programmable UPS alarm. Activated by a remote
dry contact closure.
Programmable UPS alarm. Activated by a remote
Programmable UPS alarm. Activated by a remote
dry contact closure.
Programmable UPS alarm. Activated by a remote
Programmable UPS alarm. Activated by a remote
dry contact closure.
General purpose NO and NC relay contacts.
p p
General purpose NO and NC relay contacts.
p p
Circuit Breaker CB3 Auxiliary Contact.
Circuit Breaker CB3 Auxiliary Contact
Dry contact used to activate remote transfer to
Dry contact used to activate remote transfer to
bypass.
Dry contact used to activate remote transfer to UPS.
Dry contact used to activate remote transfer to UPS
Dry contact used to activate remote EPO of UPS.
Dry contact used to activate remote EPO of UPS
DESCRIPTION:
CUSTOMER INTERFACE WIRING
INSTALLATION NOTES
DRAWING NO:
164201244---2
REVISION:
A
y
y
SHEET:
4 of 8
DATE:
051599
A ---15