Identifying Your UPS NOTE Before starting up the UPS, verify that it has been installed according to the Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide . FERRUPS UPSs come in different sizes (see Figure 1). If your UPS is a 500 VA–3.1 kVA model, continue with “Startup for the FE and...
UPS must not have an earth leakage current greater than 1.5 milliamperes. Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide ® D A N G E R W A R N I N G...
Page 10
UPS, tilsammen ikke overskride en jordafdelingsspænding på mere end 1,5 milliampere. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide C A U T I O N F A R E A D V A R S E L !
1,5 milliampère hebben. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide A D V A R S E L G E V A A R W A A R S C H U W I N G Rev A www.powerware.com...
UPS-laitteen ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 1,5 milliampeeria (mA). Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide O P G E L E T V A A R A V A R O I T U S Rev A www.powerware.com...
1,5 mA. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide V A R O D A N G E R ! A V E R T I S S E M E N T ! Rev A www.powerware.com...
Page 14
Erdschlußstrom von insgesamt 1,5 Milliampere nicht überschreiten. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide A T T E N T I O N ! W A R N U N G A C H T U N G...
Page 15
ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ ÖÕËÁÎÔÅ ÁÕÔÅÓ ÔÉÓ ÏÄÇÃÉÅÓ ÔÏ ÐÁÑÏÍ ÅÃ×ÅÉÑÉÄÉÏ ÐÅÑÉÅ×ÅÉ ÓÇÌÁÍÔÉÊÅÓ ÏÄÇÃÉÅÓ ÁÓÖÁËÅÉÁÓ Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide V O R S I C H T ! ÊÉÍÄÕÍÏÓ ÐÑÏÅÉÄÏÐÏÉÇÓÇÊ ° Rev A www.powerware.com Safety Warnings...
(95% maks.). Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Safety Warnings A T T E N Z I O N E F A R L I G F A R L I G Rev A www.powerware.com...
à terra maior que 1,5 miliampères. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide F O R S I K T I G C U I D A D O A D V E R T Ê N C I A...
эксплуатируйте устройство около воды или в местах с повышенной влажностью (макс. 95%). Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide P E R I G O О П А С Н О П Р Е Д У П Р Е Ж Д Е Н И Е...
SIE. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide О С Т О Р О Ж Н О P E L I G R O A D V E R T E N C I A...
Page 21
Ta aldrig bort nätsladden när UPS-enheten är påslagen. Detta tar bort skyddsjordningen från både UPS-enheten och den anslutna utrustningen. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Safety Warnings P R E C A U C I Ó N F A R A V A R N I N G Rev A www.powerware.com...
Page 22
Följ tillämpliga anvisningar. Batterierna måste avyttras enligt anvisningarna i lokal lagstiftning. Använda batterier får aldrig brännas upp. De kan explodera. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide V I K T I G T Rev A www.powerware.com...
UPS S TARTUP This section provides step-by-step instructions for starting the Powerware FERRUPS UPS. Follow these procedures closely to avoid potential damage to your equipment or the UPS and to protect yourself and others from hazardous operating conditions. Startup for the FE and QFE 500 VA–3.1 kVA UPS To start the FE and QFE 500 VA–3.1 kVA UPS, use the following steps:...
Page 24
NOTE For QFE models, use the supplied UPS cord to connect your equipment to the UPS output receptacles. For Hardwired UPSs: 7. Turn on the equipment that is connected to the UPS. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide AC LINE READY CHARGING BATTERY POWER Figure 2.
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation Guide. Confirm that your AC line disconnect switch and the UPS ON/OFF switch are both in the OFF position.
Page 26
[ENTER] [PROGRAM] Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Turn the AC input power on at the Turn the AC line disconnect switch to the Plug the equipment you want to Turn on the equipment connected to the Display shows: Rev A www.powerware.com...
Page 27
(Ah) for the total number of battery packs used in the UPS. If you purchased one of the FERRUPS battery pack options available from Powerware, select the Ah value from Table 1. Before programming the battery Ah, enter the user password following the instructions in “Entering Passwords”...
The UPS front panel indicators indicate how the UPS is operating and also alert you of potential power problems. Figure 7 shows the UPS front panel indicators. Table 2 explains the status of each indicator. Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide ® AC LINE READY...
Page 32
(see “Alarms” on page 59.) If you have a control panel, an alarm message appears on its display. No alarm exists. Flashing Not applicable. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Explanation Rev A www.powerware.com...
Notice that names of the operating modes appear in red on the bottom of keys 1–4. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Rev A www.powerware.com Operation...
To enter the User Password, follow these steps: Press this key: [CLEAR] [PROGRAM] [3] [7] [7] [ENTER] To clear the password, press [CLEAR] until appears on the control panel display. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Display shows: Rev A www.powerware.com...
If not, the UPS sounds alarm M, Check Battery ( indicator flashes during this part of the test. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide ). See “Alarms” on page 59. – – – ). See “Alarms” on page 59. –...
01 V In 120.7 Service 02 V Out 120.7 Service Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Parameter Name Explanation (Short Form) time System Time. The UPS uses this time to record alarms and inverter runs. When the...
Page 39
[DISPLAY] Allowed [1] [1] [ENTER] 12 SinkTemp 26c Change Not Allowed 13 --Reserved-- Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Parameter Name Explanation (Short Form) Reserved acampsiout The current your equipment is drawing from the UPS. vaout Volt-Amps Out.
Page 40
Change Not Allowed 23 InvMin 0000.0 Change Not Allowed Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Parameter Name Explanation (Short Form) xfmrtemp The temperature of the transformer. The UPS (xt) sounds an alarm and shuts down if this value is too high.
4. When it has gone into the Off mode because the batteries have been discharged during an extended outage. 5. When a system malfunction requires a UPS shutdown. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Parameter Name Explanation (Short Form) inverterlog...
Page 42
3. If the UPS is plugged in, unplug it. For hardwired models, turn the AC line disconnect switch to the OFF position. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide C A U T I O N Turn off the protected equipment. (see the label...
UPS until the AC input power returns (see “UPS Shutdown” on page 35). Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide If you have a battery cabinet that has a DC Unlock the lock in the center of the front panel and Rev A www.powerware.com...
RS-232 communication with the UPS and use commands and parameters to control UPS operation. Powerware Software Suite Each UPS ships with the Powerware Software Suite CD-ROM and a communication cable. To begin installing CheckUPS II software, refer to the instructions accompanying the Powerware Software Suite CD-ROM.
6 or 18) is for remote shutdown. The following sections describe how to take advantage of these features. Pin 20 is for option use only. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Figure 9. Communication Port t ti FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have FE 500 VA 3 1 kVA models with serial numbers 25000 and greater have FE 500 VA–3.1 kVA models with serial numbers 25000 and greater have...
RS-232 port, see Table 5 on page 40 and “Remote Monitoring” and “Remote Shutdown” on page 47. NOTE To connect a modem, see TIP 503. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Communication C A U T I O N Rev A www.powerware.com...
Page 48
Call your service representative if you need to adjust any of the settings. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Figure 10. DB-9 to UPS Pinout Figure 11. DB-25 to UPS Pinout Rev A www.powerware.com...
Page 49
Pause displays that take more than one screen. Resume scrolling. (Turn Pause off.) Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Standard Setting 25 pin D (female) wired as DCE. ASCII, 8 bits, 1 stop bit. Standard setting or Most significant bit set to 0.
*If you change parameter 39 to “Yes,” this command requires a User password. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Shows a list of all possible alarm messages, the audio code and letter for each alarm and whether the alarm is active.
Page 51
*If you change parameter 39 to “Yes,” this command requires a User password. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Function Displays system time and date. To set the date, enter Delays next command when you enter a number after represents 2.5 milliseconds, so...
Page 52
*If you change parameter 39 to “Yes,” this command requires a User password. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Function Displays all parameters and their keywords (the names you can use with commands). You can also display a range of parameters by entering the numbers or names of the starting and ending parameters.
UPS displays “Emergency PwrOff.” Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Function Starts a system test of the logic, inverter and battery. Shows the current UPS time. To set the time, enter the command.
Page 54
You can also set up the UPS to restart automatically when the shutdown signal stops. See TIP 503 or contact your service representative for more information. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Rev A www.powerware.com...
C H A P T E R 6 PTIONS Powerware offers many options for your FERRUPS UPS. If you would like more information, contact your local Powerware office or distributor. Bypass Switches If your UPS does not have a plug, a bypass switch lets you transfer your protected equipment to direct AC input power conveniently when it’s...
Check and record the values of the first 19 parameters while the UPS is online and on battery. For more information on preventive maintenance checks, contact your service representative. Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide ® Rev A www.powerware.com...
Page 61
FE and QFE 10 kVA, 12.5 kVA, and 18 kVA models do not have internal batteries. Batteries are in a separate battery cabinet or rack. If your model has an internal bypass switch, add 8” (20.0 cm) to the depth. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide 7 kVA/ 10 kVA/ 5 kW 7.5 kW...
Page 62
Electrical Code Article 250-5d, with output neutral bonded to ground. There is no direct Bonding connection between input and output, and less than 2 pF of effective input to output capacitance. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Rev A www.powerware.com...
Page 63
5A. Type Standard batteries are sealed, gas recombinant, lead-acid type, especially designed for UPS use. Optional battery chargers at higher current ratings are available. Call your local Powerware office or distributor for more information. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide 20°...
NOTE If you do not turn the alarm beep back on, the UPS is not able to sound an alarm code the next time there is an alarm. Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide ® Turn the Alarm Silence Switch on Press [CTRL]-[5] [ENTER] [ENTER] Rev A www.powerware.com...
Page 66
Temp UPS shuts down. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide What To Do Wait for AC input power to be restored. When AC input power returns, turn on the UPS. The CHARGING indicator illuminates as the UPS begins recharging batteries.
Page 67
The input voltage is higher than the alarm Input setting. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Troubleshooting What To Do To start the user test alarm from the control panel, press [CTRL]-[8] [ENTER] [ENTER]. Repeat the procedure to turn the alarm off.
Use this key: [1] through [9] Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide What To Do The UPS shuts down. Contact your service representative. The UPS may have shut down; if so, contact your service representative. If the UPS has not shut down, shut down your equipment or bypass the UPS;...
February 5 (2/5). “0951” means the inverter ran at 9:51 a.m. “0015” means the inverter ran for 0 hours and 15 minutes. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide To do this: Pause the scrolling and start it again. Go to the next log entry.
You can also display parameter 25 to view the Alarm Log; this display is the same as the control panel display. Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide Meaning Explanation System Test UPS went to inverter to test the batteries.
NOTE For critical applications, immediate replacement may be available. Call the for the dealer or distributor nearest you. Help Desk Powerware ® FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide at one of the following telephone numbers Help Desk Rev A www.powerware.com Local...