Powerware Uninterruptible Power Supply Installation And Operation Manual page 141

Uninterruptible power supply 500 kva -- 750 kva
Table of Contents

Advertisement

8.
Terminals E1 through E12 are 2-hole bus bar mountings for standard NEMA 2-hole barrel
lugs. Refer to Table D for power cable terminations, Table E for conduit requirements, and
Table F for recommended installation parts and tools not supplied by Powerware. Drawing
164201244---7 shows the location of the power cable terminals inside the UPS.
Terminal Function
AC Input to UPS
p
Rectifier
(CB1 Input)
(CB1 Input)
AC Input to Module
p
Bypass (UPS
Bypass)
Bypass)
AC Output from
p
Inverter to Module
Bypass or SBM
Bypass or SBM
AC Input to Module E9
p
Bypass from
Inverter
Inverter
AC Output to
p
Critical Load from
Module Bypass
Module Bypass
DC Input from
p
Battery to UPS
DC Link Output
from Rectifier to
from Rectifier to
Inverter
DC Link Input to
Inverter from
Inverter from
Rectifier
Neutral, Output
Customer Ground
NOTE: Customer ground, size 2/0, can be
run in any conduit listed in Table E.
Powerware 9315 (500 kVA- -750 kVA) Installation and Operation
164201244 REV. D 030101
Table D. UPS Cabinet Power Cable Terminations
Terminal
E1
Phase A
E2
Phase B
E3
Phase C
E6
Phase A
S
E7
Phase B
E8
Phase C
E9
Phase A
E10
Phase B
E11
Phase C
E12
Neutral
Phase A
E10
Phase B
E11
Phase C
E12
Neutral
E9
Phase A
E10
Phase B
E11
Phase C
E4
Battery (+) 6 --- 2 bolt mounting
S
E5
Battery (---) 6 --- 2 bolt mounting
(+)
DC Link (+) 6 --- 1 bolt mounting
(---)
DC Link (---) 6 --- 1 bolt mounting
Inverter (+) DC Link (+) 6 --- 1 bolt mounting
Inverter (---) DC Link (---) 6 --- 1 bolt mounting
E12
Neutral
Ground
Ground
Function
Bus Landings
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 1 bolt mounting
4 --- 1 bolt mounting
4 --- 1 bolt mounting
4 --- 1 bolt mounting
12 --- 2 bolt mounting
4 --- 2 bolt mounting
4 --- 2 bolt mounting
12 --- 2 bolt mounting
8 --- 2 bolt mounting
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
REVISION: C
Tightening
Torque
N-M (lb-ft)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
76 (56)
164201244---1
DATE:
021500
Bolt
Size
(In.)
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
SHEET:
4 of 10
A ---5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Uninterruptible Power Supply and is the answer not in the manual?

This manual is also suitable for:

9315

Table of Contents