Chapter 5
Staff/duty stations
96
Code blue calls
Press the Code button on the staff/duty station to send a code blue
call to staff consoles and annunciators. Pressing Code causes the
following to happen:
Lights by the staff/duty station Code button and by any linked
Code button turn on to confirm code blue call placement.
The Call status light on the staff/duty station turns on to confirm
nurse call placement.
The call assurance tone sounds at the staff/duty station.
All light sections of associated corridor and zone lights fast flash
blue.
Associated zone lights emit a very fast, repeating buzz.
Code blue tones sound at staff consoles and annunciators, and
at stations where staff follow is active.
A code blue nurse call row appears on the Call screen on staff
consoles, emergency annunciators, and unit annunciators.
Staff emergency calls
Press the Emerg button on the staff/duty station to send a staff
emergency call to staff consoles and annunciators. Pressing Emerg
causes this to happen:
Lights by the staff/duty station Emerg button and by any linked
Emerg button turn on to confirm staff emergency call
placement.
The Call status light on the station turns on to confirm nurse call
placement.
The call assurance tone sounds at the staff/duty station.
Top sections of associated corridor and zone lights fast flash
red.
Associated zone lights emit a very fast, repeating buzz.
Staff emergency tones sound at staff consoles and
annunciators, and at stations where staff follow is active.
A staff emergency nurse call row appears on the Call screen on
staff consoles, emergency annunciators, and unit annunciators.
Staff normal calls
Press the Assist button to send a staff normal call to staff consoles
and annunciators. Pressing Assist on the staff/duty station causes
the following to happen:
The Assist status light and the Call status light on the staff/duty
station turn on to confirm placement of the staff normal call.
The call assurance tone sounds at the staff/duty station.
Telligence Patient-Staff Communication System Operation Manual