Input 1 Set Up Wiring; Table 6-3 Set Up Wiring Procedure For Thermocouple Inputs Using An Ice Bath; Table 6-4 Set Up Wiring Procedure For Thermocouple Inputs Using Thermocouple Source; Figure 6-2 Wiring Connections For Thermocouple Inputs Using An Ice Bath - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

6.4 Input 1 Set Up Wiring

Thermocouple Inputs Using an Ice Bath
Refer to Figure 6-2 and wire the controller according to the procedure given in Table 6-3.
Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Table 6-3 Set Up Wiring Procedure for Thermocouple Inputs
Step
Connect the copper leads to the calibrator.
1
Connect a length of thermocouple extension wire to the end of each copper lead and
2
insert the junction points into the ice bath.
3
Connect the thermocouple extension wires to the terminals for Input #1.
See Figure 6-2.
Millivolt
Source
Copper Leads

Figure 6-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath

Thermocouple Inputs Using a Thermocouple Source
Refer to Figure 6-3 and wire the controller according to the procedure given in Table 6-4.
Make sure the jumper at S101 is in the #1 position (Figure 2-2).
Table 6-4 Set Up Wiring Procedure for Thermocouple Inputs using
Step
Connect the thermocouple extension wires to the terminals for Input #1 as shown in
1
Figure 6-3.
Figure 6-3 Wiring Connections for Thermocouple Inputs Using
1/01
Using an Ice Bath
+
_
Thermocouple Source
+
Thermocouple
_
Source
Thermocouple
Extension Wire
Thermocouple Source
UDC2300 Limit Controller Product Manual
Action
Ice Bath
Action
Input Calibration
+
8
_
7
24872
Thermocouple
Extension Wire
8
+
_
7
24873