Input Calibration

5.4 Input 1 or 2 Set Up Wiring

5.4.1 Thermocouple Inputs Using an Ice Bath

Refer to Figure 5-2 and wire the controller according to the procedure given in Table 5-3.
Table 5-3 Set Up Wiring Procedure for Thermocouple Inputs
Step
1
Connect the copper leads to the calibrator.
Connect a length of thermocouple extension wire to the end of each copper lead and
2
insert the junction points into the ice bath.
Connect the thermocouple extension wires to the terminals for Input #1.
3
See Figure 5-2.
Millivolt
Source
Copper Leads

Figure 5-2 Wiring Connections for Thermocouple Inputs Using an Ice Bath

136
Using an Ice Bath
+
_
Ice Bath
UDC3200 Universal Digital Controller Product Manual
Action
Thermocouple
Extension Wire
22
23 +
Input 2
24 -
25
26 +
Input 1
27 -