Single Load Connections - Agilent Technologies N8900 series Operating Manual

Autoranging system dc power supply
Table of Contents

Advertisement

Connections-Single Unit
AWG
2
1/0
2/0
3/0
4/0
Note 1. Ampacity is based on a single conductor in free air, 26-30 °C ambient temperature, with the conductor rated at
60 °C. Ampacity ratings decrease when wires are bundled an at higher ambient temperatures.
Note 2. Resistance is in ohms/1000 feet, at 20 °C wire temperature.
Along with conductor temperature, you must also consider voltage drop when selecting wire sizes. Although the power
supply will compensate for the voltage in the load wires, it is recommended to minimize the voltage drop as much as
possible to prevent excessive output power consumption from the power supply and poor dynamic response to load
changes. Larger diameter wire sizes will help minimize load-wire voltage drops. Twisting or bundling load wires will help
reduce transient voltage drops.

Single Load Connections

As shown in the following figure, terminate all load wires with the proper wire terminal lugs securely attached. DO
NOT use unterminated wires when making connections at the power supply. Also ensure that the mounting hardware
does not short the output terminals.
The following figure illustrates the recommended hardware sizes. A hardware kit is shipped with your unit. You must
provide the cables and terminations. Ensure that the cable-mounting hardware does not short the output terminals.
Use the M8 diameter bolts, nuts, ring lugs, and
washers - for models rated up to 200 V
30
Nearest Metric size
35 mm 2
50 mm 2
70 mm 2
95 mm 2
120 mm 2
Ampacity (Note1)
up to 140 A
up to 195 A
up to 225 A
up to 260 A
up to 300 A
Use the M6 diameter bolts, nuts, ring lugs, and
washers - for models rated 500 V and up
Agilent N8900 Series Operating and Service Guide
Resistance (Note2)
0.156
0.098
0.078
0.062
0.049

Advertisement