Agilent Technologies N8900 series Operating Manual page 13

Autoranging system dc power supply
Table of Contents

Advertisement

Specifications and Characteristics
Supplemental Characteristics (typical)
Characteristic 10 kW
Programming Range
    Voltage:
    Current:
Programming and Meas-
urement Resolution
    Voltage:
    Current:
Temperature Coefficient 1
    Voltage:
    Current:
Output response time 2
    Up, full load:
    Down, full load:
    Down, no load:
Over-voltage protection
range
Remote sense com-
pensation per load lead
Source regulation 2
    Voltage:
    Current:
Output ripple & noise 3
    CC rms:
AC Input
    Nominal Ratings:
    Input Range:
    Frequency:
    Phase:
    Input Current:
    Inrush Current:
    Power Factor:
    Efficiency:
12
N8925A
N8926A
N8945A
N8946A
0 to 81.6 V
0 to 204 V
0 to 346.8 A
0 to 142.8 A
4 mV
9 mV
14 mA
6 mA
4 mV
10 mV
17 mA
7 mA
≤ 30 ms
≤ 30 ms
≤ 80 ms
≤ 80 ms
≤ 30 s / 40 s
≤10 s
0 to 88 V
0 to 220 V
2 V
5 V
16 mV
40 mV
170 mA
70 mA
160 mA
44 mA
208 VAC for N892xA; 400 VAC for N894xA
L1 - 56 A; L2, L3 - 32 A for N892xA; L1 - 28 A; L2, L3 - 16 A for N894xA
pending for N892xA; 49 A for N894xA
> 0.99 at nominal input and rated power
N8928A
N8948A
0 to 510 V
0 to 61.2 A
21 mV
3 mA
25 mV
3 mA
≤ 30 ms
≤ 80 ms
≤10 s
0 to 550 V
10 V
100 mV
30 mA
32 mA
± 10 % of nominal rating
50/60 Hz
3-phase
87.5 % - 93.5 %
Agilent N8900 Series Operating and Service Guide
N8929A
N8930A
N8949A
N8950A
0 to 765 V
0 to 1020 V
0 to 40.8 A
0 to 30.6 A
31 mV
41 mV
2 mA
2 mA
37.5 mV
50 mV
2 mA
1.5 mA
≤ 30 ms
≤ 30 ms
≤ 80 ms
≤ 80 ms
≤10 s
≤10 s
0 to 825 V
0 - 1100 V
18 V
22 V
150 mV
200 mV
20 mA
15 mA
32 mA
22 mA