Agilent Technologies N8900 series Operating Manual page 12

Autoranging system dc power supply
Table of Contents

Advertisement

Supplemental Characteristics (typical)
Characteristic 5 kW
Programming Range
    Voltage:
    Current:
Programming and Meas-
urement Resolution
    Voltage:
    Current:
Temperature Coefficient 1
    Voltage:
    Current:
Output response time 2
    Up, full load:
    Down, full load:
    Down, no load:
Over-voltage protection range
Remote sense compensation
per load lead
Source regulation 2
    Voltage:
    Current:
Output ripple & noise 3
    CC rms:
AC Input
    Nominal Ratings:
    Input Range:
    Frequency:
    Phase:
    Input Current:
    Inrush Current:
    Power Factor:
    Efficiency:
Agilent N8900 Series Operating and Service Guide
N8920A
N8921A
N8940A
N8941A
0 to 81.6 V
0 to 204 V
0 to 173.4 A
0 to 71.4 A
4 mV
9 mV
7 mA
3 mA
4 mV
10 mV
8.5 mA
3.5 mA
≤ 30 ms
≤ 30 ms
≤ 80 ms
≤ 80 ms
≤ 30 s
≤10 s
0 to 88 V
0 to 220 V
2 V
5 V
16 mV
40 mV
85 mA
35 mA
80 mA
22 mA
208 VAC for N892xA; 400 VAC for N894xA
± 10 % of nominal rating
L2, L3 - 32 A for N892xA; L2, L3 - 16 A for N894xA
pending for N892xA; 28 A for N894xA
> 0.99 at nominal input and rated power
Specifications and Characteristics
N8923A
N8943A
0 to 510 V
0 to 30.6 A
21 mV
2 mA
25 mV
1.5 mA
≤ 30 ms
≤ 80 ms
≤10
0 to 550 V
10 V
100 mV
15 mA
16 mA
50/60 Hz
3-phase
87.5 % - 93.5 %
N8924A
N8944A
0 to 765 V
0 to 20.4 A
31 mV
1 mA
37.5 mV
1 mA
≤ 30 ms
≤ 80 ms
≤10
0 to 825 V
18 V
150 mV
10 mA
16 mA
11

Advertisement

Table of Contents
loading

Table of Contents