Configuration Options; Start-Up; Actual Start-Up; Operating Limitations - Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

START-UP
Do not manu_dly operate contactors. Serious damage to the
machine may result.
Actual Start-Up-
Actual
start-_q) should be done only
under Sul)eia'ision o/ a quali/ied
r@'igerution
Wchniciun.
1. Be sure all oil, discharge,
suction
service
valves
(if
equipped) and liquid line service valves are open.
2. Using the Navigato( r_'rdisplay, set leaving-fluid
set point
(Set PoOlt_COOL_4JSP.I).
No cooling
range adjust-
ment is necess_uy.
3. If optional
control
functions
or accessories
_ue being
used, the unit must
be properly
configured.
Refer to
Configuration
Options section for details.
4. Complete the Start-Up Checklist to verily all components
ale operating properly.
5. Turn Enable/Off/Remote
contact switch to Enable position.
6. Allow
unit to operate
and confirm
that everything
is
functioning
properly.
Check
to see that leaving
fluid
temperature
aglees with leaving
set point Control
Point
(Run Status ---)VIEW_4JTPT).
Operating
Limitations
TEMPERATURES-
Unit operating
temperature
limits are
listed in Table 27.
Table 27 -- Temperature
Limits for Standard Units
TEMPERATURE
1F5
C
Maximum Ambient Temperature
52
Minimum Ambient Temperature
32
0
Maximum Cooler EWT*
_095
35
Maximum Cooler LWT
60
15
Minimum Cooler LWTt
4.4
LEGEND
EWT --
Entering Fluid (Water) Temperature
LWT --
Leaving Fluid (Water) Temperature
*For sustained operation,
EWT should not exceed 85 F (29.4 C).
1-Unit
requires
brine
modification
for
operation
below
this
temperature.
Low Ambient
Temperature
Operation
--
If unit operating
temperatures
below 32 F (0 ° C) are expected,
refer to separate
unit installation
instructions
for low ambient temperature
oper-
ation using accessory
low ambient temperature
head pressure
control, if not equipped.
Contact your C_urier representative
for
details.
NOTE: If wind velocity is expected
to be greater than 5 mph
(8 kin/h) wind baffles and brackets
must be field-fabricated
and installed
for all units using accessory
low ambient
head
pressure control. See the 30XA Installation
Instructions
or the
low ambient
temperature
head
pressure
control
accessory
installation
instructions
for more information.
Brine duty application
(below
40 F [4.4 C] LCWT)
for
chiller normally
requires
factory modification.
Contact a
Canier
Representative
for
details
regarding
specific
applications.
Operation
below 40 F (4.4 C) LCWT with-
out modification
can result in compressor
failure.
VOLTAGE
Muin Power Supply --
Minimum
and maximum
acceptable
supply voltages are listed in the Inst_dlation Instructions.
Unbalanced
3-Phase Supply Voltuge -- Never operate a motor
where a phase imb_dance between phases is greater than 2%.
To determine
percent voltage imb_dance:
max voltage deviation from
avg voltage
% Voltage Imbalance = 100 x
average voltage
The maximum
voltage deviation
is the largest difference
between a voltage measurement
across 2 legs and the average
across _dl 3 legs.
Example: Supply voltage is 240-3-60.
AB = 243v
A
B
C
BC = 236v
K
I "_
AC = 238v
1. Determine
average voltage:
Average voltage
=
m
z
243+236+238
3
717
3
239
2. Determine
maximum
deviation from average voltage:
(AB) 243 - 239 = 4 v
(BC) 239 - 236 = 3 v
(AC) 239 - 238 = 1 v
Maximum
deviation is 4 v.
3. Determine
percent voltage imbalance:
4
% Voltage hnbalance
= 100 x
23----7
= 1.7%
This voltage imbalance
is satisfactory
as it is below the
maximum
allowable of 2%.
IMPORTANT:
If the supply voltage
phase imbal-
ance is more than 2%, contact
the local electric
utility company
immediately.
Do not operate unit
until imbalance
condition
is corrected.
MINIMUM
FLUID
LOOP VOLUME
-- To obtain
proper
temperature
control, loop fluid volume must be at least 3 gal-
lons per ton (3.25 L per kW) of chiller nominal capacity for air
conditioning
and at least 6 gallons per ton (6.5 L per kW) for
process applications
or systems that must operate at low ambi-
ent temperatures
(below 32 F [0 ° C]). Refer to application
in-
formation
in Product Data literature for details.
FLOW RATE REQUIREMENTS
-- Standard chillers should
be applied
with nominal
flow rates within those listed in the
Minimum
and Maximum
Cooler Flow Rates table. Higher or
lower flow rates are permissible
to obtain
lower or higher
temperature
rises. Minimum
flow rates must be exceeded
to
assure turbulent flow and proper heat transfer in the coolel: See
Table 28. See Fig. 22A-22C for cooler pressure drop curves.
Operation
below
minimum
flow
rate
could
generate
alarms, which could result in &_mage to the coolel:
Consult
application
&_ta section
in the Product
Data
literature and job design requirements
to determine
flow rate
requirements
for a particular inst:dlation.
42

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents