Repeated
High Discharge
Gas Overrides
Aimin 90 -- Circuit A (R37)
Almm 91 -- Circuit B (R38)
Akum 92 -- Circuit C (R39)
Cdwriafor
Trip --
The criterion is tested when file circuit is
ON. This _flarm will be tripped if the circuit capacity is reduced
more than 8 times in 30 minutes due to high discharge gas tem-
peratures.
If no override
occurs
in a 30-minute
period,
the
counter is reset.
A_Tion to be Taken -- The affected circuit will be shut down.
Reset Method
-- Automatic,
after 30 minutes. If file alann
is
cleared
via the Manual
method,
the counter
will be reset to
zero.
Possible Causes -- If this condition
is encountered,
check the
following items:
•
Maximum
Condensing
Temperature
(MCT)
for
the
proper setting
•
noncondensables
in the refrigerant
circuit
•
condenser
air re-circulation
•
proper refrigerant
charge (overcharged)
•
operation
beyond
the limit of the machine
•
condenser
coils for debris or restriction
•
condenser
fans
and
motors
for
proper
rotation
and
operation
•
discharge
service
valve to be sure that it is open. Check
the discharge
pressure
transducer
for accuracy
•
confirm
unit configuration
Repeated
Low Suction
Temperature
Protection
Aimin 93 -- Circuit A (R40)
Almm 94 -- Circuit B (R41)
Akum 95 -- Circuit C (R42)
CriWriafbr
Trip --
The criterion is tested when file circuit is
ON. If the circuit operates and if more than 8 successive
circuit
capacity
decreases
(stop
the
compressor)
have
occurred
because
of low suction temperature
protection
ovemdes,
the
circuit almm will be tripped. If no override has occurred
for
more fllan 30 minutes, the override counter will be reset to zero
(LOSP).
Action to be Taken -- ALARM_LED
will be set to blinking.
Alert rekiy will be energized.
Reset Method -- Automatic,
when the override counter returns
to zero. If the almm is clemed
via file Manual
method,
the
counter will be forced to zero.
Possible Causes -- If this condition
is encountered,
check the
following items:
•
suction transducer
for accuracy
•
suction transducer
wiring
•
EXV operation
•
proper refrigerant
charge (undercharged)
•
evaporator
loop for low water flow
•
evaporator
leaving
water temperature
•
suction
service
valve
to be sure it is open.
Discharge
pressure transducer
for accuracy
•
confirm
unit configuration
Alarm 96 -- Low Entering
Water Temperature
in Heating
NOTE: Alarm 96 is not used or supported.
If this condition
is
encountered,
confirm machine configuration.
Condenser
Default
Alm'm 97 -- Pump 1 (R73)
Aku'm 98 -- Pump 2 (R74)
NOTE:
Alarms
97 and 98 are not used or supported.
If this
condition is encountered,
confirm machine configuration.
High Discharge
Temperature
Alarm 99 -- Circuit A (R78)
Alarm 100 -- Circuit B (R79)
Alarm 101 -- Circuit C (R80)
Criteria for Trip -- Tile criterion is tested when file compressor
is operating. This almm will be tripped if the dischmge gas tem-
perature is higher than 212 F (100 C) for more than 90 seconds.
Action
to be Taken
--
The
affected
compressor
will
be
stopped.
Reset Method--
Manual.
Possible Causes -- If tiffs condition is encountered,
check the
following items:
•
Maximum
Condensing
Temperature
(MCT)
for
the
proper setting
•
noncondensables
in the refrigerant
circuit
•
condenser
air re-circulation
•
proper refrigerant
charge (overcharged)
•
operation
beyond
the limit of the machine
•
condenser
coils for debris or restriction
•
condenser fans and motors for proper rotation and operation
•
the discharge
service
valve
to be sure that it is open,
check the discharge
pressure
transducer
for accuracy
•
confirm
unit configuration
Low Economizer
Pressure
Alarm 102 -- Circuit A (R81 )
Alarm 103 -- Circuit B (E82)
Alarm 104 -- Circuit C (R83)
Criwria.for
Tril) -- The criterion is tested when the compres-
sor is operating
to prevent pumpdown
conditions
when the
suction service valve is closed. This alarm will be tripped if the
economizer
pressure is below the suction pressure more than
1 bar (14.5 psi) for more than 10 seconds.
Action
to be Taken
--
The
affected
compressor
will
be
stopped.
Reset Method--
Manual.
Possible Causes -- If fills condition is encountered,
check the
following items:
•
suction service valve is closed
•
sensor wiring to the EXV boards
•
boards for faulty channels
•
faulty transducer
•
economizer
EXV operation
Slide Valve Control
Unverifiable
Alarm 105 -- Circuit A (R87)
Alarm 106 -- Circuit B (E88)
Alarm 107 -- Circuit C (R89)
Criwria.for
TriF -- The criteria are tested when the compres-
sor is operating.
This alarm will be tripped if:
•
The circuit is operating
at 100% of capacity
and the mea-
sured current is less than 1.15 times the current at fully
unloaded
30% for more than one minute.
•
The circuit
is operating
and is at a minimum
load (30%
of capacity)
and the measured
current is greater than 0.78
expected
current at 100% of capacity.
Action to be Taken -- The affected compressor
will continue to
lain.
Reset Method--
Manual.
Possible Causes -- If tiffs condition is encountered,
check the
following items:
•
faulty unloader
solenoid
valves
•
faulty unloader
solenoid
coils
•
wiring of the unloader
solenoid
valves
•
CPM board for faulty channels
•
current transformer
reading for accuracy
79