Alarm
108 -- Cooler Flow Switch Setpoint
Configuration
Failure _R90)
NOTE: Almm 108 is not used or supported.
If this condition
is
encountered,
confirm machine configuration.
Alarm
109 -- Cooler Flow Switch Failure (R91 )
Criteria for Trip -- The criteria are tested when the unit is on
or off. This alann will be tripped when the unit is on if:
The flow switch fails to close after the Off/On delay.
If the master/slave
control
is active,
the unit is the lag
chiller and if the cooler flow switch fails to close within
one minute
after the cooler
pump
was restarted.
The
alarm is ignored
if the lag cooler pump
is stopped
as a
result of master/slave
control.
The flow switch is opened
during normal operation.
The alarm will be tripped when the unit is off if:
The cooler
pump control
is enabled
(PUMP=0)
and the
cooler flow switch is checked
when the pump is enabled
(RLOC) and the cooler flow switch is closed after file cooler
pump is commended
OFF for more than 2 minutes.
The flow switch fails to close after the Off/On delay after
the cooler pump has been turned off to protect the cooler
from freezing
(PUMP=0).
Action to be Taken -- For criteria for trip AI and A2, the com-
pressors will not be st_uted.
For criteria for trip A3, all compressors
will be stopped wifllout
going through pumpdown.
Cooler pump will be stopped with
no delay.
For criteria for trip BI, the unit will not start.
Reset Method --
Manual if at least one compressor
is operat-
ing. Automatic
if no compressors
are operating.
Possible Causes -- If this condition
is encountered,
check the
following
items:
a faulty flow switch
flow switch wiring
Main Base Board for a faulty channel
Alarm
110 -- Service
Maintenance
Alert (Sl:nn)
CriWriafor
Trip -- This alert is tested whether the unit is ON
or OFF and when file Servicing
Alert decisions
listed under
Time Clock--)MCFG
have been enabled.
The almm will be
generated
if the one of the following
configuration
errors is
detected by the control. The "nn" refers to the error code listed
in Table 42.
Table 42 -- Service Maintenance Alert Codes
CODE
DESCRIPTION
Sr-01
Circuit A Loss of Refrigerant
Charge
Sr-02
Circuit B Loss of Refrigerant
Charge
Sr-03
Circuit C Loss of Refrigerant Charge
Sr-04
Water Loop Size Warning
Sr-05
Air Exchanger Cleanliness Warning
Sr-06
Cooler Pump 1 Servicing Required
Sr-07
Cooler Pump 2 Servicing Required
Sr-08
Condenser
Pump 1 Servicing Required
Sr-09
Condenser
Pump 2 Servicing Required
Sr-10
Water Filter Servicing Required
Sr-11
Compressor
A Oil Filter Servicing Required
Sr-12
Compressor
B Oil Filter Servicing Required
Sr-13
Compressor
C Oil Filter Servicing Required
Action m be Taken -- None.
Reset Method--
Manual, after the service has been completed.
Possible
Causes
--
If the Sr-01, 02, or 03 conditions
me
encountered,
check the following items:
sensor wiring to the Main Base Board
sensor for accuracy
Compressor
Motor Temperature
Too High
Almm 111-01 -- Circuit A (A1.01 )
Almm 112-01 -- Circuit B (B 1.01 )
Almm 113-01 --Circuit
C (CI.01)
CriWria .for Trip --
The alarm criteria me checked
when the
compressor
is ON. This alarm will be generated
if:
The temperature
is greater
than 250 F (121 C) and it has
been
greater
than 212 F (100 C) for
10 consecutive
seconds.
The
compressor
temperature
is greater
than
232
F
(111 C) for 90 seconds
(but less than 250 F [121 C]).
Action to be _iken -- The circuit shuts down immediately.
Reset Method -- Manual
Possible Causes -- If this condition
is encountered,
check the
following items:
faulty wiring and loose plugs
faulty CPM board
Compressor
Motor Temperature
Out of Range
Alarm 111-02 -- Circuit A (A1.027
Almm 112-02 --Circuit
B (BI.02)
Almm 113-02-
Circuit C (C 1.027
Criteria .for Trip --
The alarm criterion
is checked
when the
compressor
is ON. This alarm will be generated if: the temper-
ature is greater than 250 F (121 C) and it has NOT been greater
than 212 F (100 C) for 10 consecutive
seconds.
Action to be _ken
-- The compressor
will be stopped.
Reset Method -- Manual
Possible Causes -- ff this condition
is encountered,
check the
following items:
faulty compressor
temperature
thermistor
faulty wiring and loose plugs
faulty CPM board
Compressor
High Pressure
Switch
Protection
Almm 111-03 -- Circuit A (A1.03)
Almm 112-03 --Circuit
B (BI.03)
Almm 113-03 --Circuit
C (C 1.03)
Criteria.for
Trip --
The alarm criterion
is checked
when the
compressor
is ON. This alarm will be generated
if the circuit
high-pressure
switch (HPS) opens for more than 200 ms (milli-
seconds). The CPM board monitors the HPS switch.
A_Tion to be _ken
-- The compressor
will be stopped.
Reset Method -- Manu_fl
Possible Causes -- ff this condition
is encountered,
check the
following items:
condenser
fan or contactor failure of loss of condenser
air
flow
compressor
operating
beyond
the operation
envelope
faulty high pressure
switch or wiring
faulty CPM board
Compressor
Overcurrent
Almm 111-04 -- Circuit A (A1.04)
Almm 112-04 --Circuit
B (BI.04)
Almm 112-04 -- Circuit C (C 1.04)
CriWria.for
Trip --
The alarm criterion
is checked
when the
compressor
is ON. This _flmm will be generated
if the CPM
bomd detects a high motor current compared
with the MTA
(must trip amps) setting for more than 1.7 seconds.
A_tion to be Taken -- The compressor
will be stopped.
Reset Method -- Manu_d
80