Possible Causes -- This mode is in effect only due to the Min-
utes Off Time timel:
MODE
2 (MD02) -- Second Setpoint in Use
Criteria
for Mode -- Tested when the unit is ON. This mode
is active
when
Cooling
Setpoint
2 (Setpoints--cCOOL--€
CSP.2)
or Ice Setpoint
(Setpoints_COOL_CSP3)
is in
use. While
in this mode, the Active
Setpoint
(Run
Status
--+VIEW--cSETP)
will show the CSP.2 or CSP.3 value.
Action Taken -- The unit will operate to the Cooling Setpoint
2 (CSP.2) or Ice Setpoint (CSP.3).
Termination
-- This mode will terminate
when the Cooling
Setpoint 2 (CSP.2) or Ice Setpoint (CSP.3) is no longer in use.
Possible Causes
--
This mode is in effect only due to pro-
grmnming
options.
MODE
3 (MD03) -- Reset in Effect
Criteria
for Mode -- Tested when the unit is ON. This mode
is active when Temperature
Reset (Configuration--¢RSET--€
CRST)
is enabled either by CRST=I
(Outside Air Tempera-
ture), CRST=2
(Return Water), CRST=3
(4-20 mA Input), or
CRST=4
(Space Temperature)
and is active.
Action Taken
--
The Active
Setpoint
(Run Status--cVIEW
---_S'ETP) will be modified
according
to the progrmnmed
information
and will be displayed
as the Control
Point (Run
Status --+VIEW _CTPT).
Termination
-- This mode will terminate when the Tempera-
ture Reset is not modifying
the active leaving water set point,
so SETP
is the same as CTPT.
Possible Causes
--
This mode is in effect only due to pro-
grmnming
options.
MODE
4 (MD04) -- Demand Limit Active
Criteria
for Mode -- Tested when the unit is ON. This mode
is active
when
Demand
Limit
(Configuration--cRSET--€
DMDC)
is enabled either by DMDC=I
(Switch),
DMDC=2
(4-20 mA Input) or the Night Time Low Sound Capacity Limit
((;bnfiguration
_OPTN
---)LS.LT).
Action Taken
--
The Active
Demand
Limit
Value
(Run
Status--_VIEW--_LIM)
will display the current demand
limit
according
to the progrmnmed
information
and the unit's capac-
ity will be reduced to the mnount shown or lower
Termination
-- This mode will terminate
when the Demand
Limit command
has been lemoved.
Possible Causes
--
This mode is in effect only due to pro-
grmnming
options.
MODE
5 (MD05) -- Ramp Ixmding Active
Criteria
for Mode -- Tested when the unit is ON. This mode
is
active
when
Ramp
Loading
(Cot_guration_OPTN
_RLS)
is enabled and the following
conditions
are met:
1. The leaving water temperature
is more than 4 ° F (2.2 ° C)
from the Control
Point (Run Status-+VIEW_CTPT),
and
2. The rate of change of the leaving
water temperature
is
gleater
than the Cool
Ramp
Ixmding
(Set Points--+
COOL _CRMP).
Action Taken -- The control will limit the percent capacity in-
crease until one of the two conditions in Mode 5 is no longer tree.
Termination
-- This mode will terminate
once either condi-
tions in Mode 5 is no longer tree.
Possible Causes
--
This mode is in effect only due to pro-
grmnming
options.
MODE
6 (MD06) -- Cooler Heater Active
Criteria
for Mode --
Tested whether the unit is ON or OFF.
This mode is active when the cooler heater is energized,
if the
Outdoor Air Temperature (Temperature_UNIT_OAT)
is
less than the calculated wdue, (Freeze Setpoint + Cooler Heater
Delta T Setpoint [Configuration_SERV--cHTR]
default
- 2° F [1.1° C]) and either the Leaving Water Temperature
(Temperature --+UNIT --+LWT)or the Entering Water Ternper-
ature (Temperature--+UNIT--+EWT) are less than or equ:d to
the Freeze Setpoint + Cooler Heater Delta T Setpoint (HTR).
The Freeze Setpoint is 34 F (1.1 C), for fresh water systems
(Configuration _SERV--)FLUD=I).
The Freeze Setpoint is
Brine Freeze Setpoint (Configuration_SERV--_LOSP),
for
Medium Temperature Brine systems, ((_bnfiguration ---_SERV
-+FLUD=2).
Action Taken -- The cooler heater will be energized.
Termination -- The cooler heater will be deenergized when
both the Entering Water Temperature (EWT) and Leaving
Water Temperature (LWT) are above the Freeze Setpoint +
Cooler Heater Delta T Setpoint (HTR).
Possible Causes -- This mode will be enabled for fieeze pro-
tection. If the temperatures tu'e not as described above, check
the accuracy of the outside ail; entering and leaving water
thermistors.
MODE
7 (MD07)
-- Cooler Pumps Rotation
Criteria
for Mode -- Tested whether the unit is ON or OFE
This mode is active when the Cooler Pump Sequence (Configu-
ration _OPTN---)PUMP=2)
(2 Pumps Automatic Changeover)
and the Pump Rotation
Delta Timer ((_bnfiguration
_OPTN
--¢ROZP) has expired.
Action Taken --
The control will switch the operation
of the
pumps.
The lead pump will be operating
normally.
The lag
pump will be stmted, becoming
the lead, and then the origimd
lead pump will be shut down.
Termination
--
This mode will terminate
when
the pump
operation has been completed.
Possible
Causes
-- This mode is in effect only due to pro-
gmmming
options.
MODE
8 (MD08)
-- Pump Periodic Start
Criteria
for Mode
--
This mode is active when
the cooler
pump
is started
for the Periodic
Pump
Start configuration
(Configuration
Mode --€ OPTN---)PM.PS=YES).
Action Taken -- If the pump has not run that day, a pump will
be started and will run for 2 seconds at 2:00 PM. If the machine
is equipped with dual pumps, Pump no. 1 will mn on even &tys
(such as day 2, 4, 6 of the month). Pump no. 2 will run on odd
days (such as day 1,3, 5 of the month).
Termination
--
This mode will terminate
when
the pump
shuts down.
Possible
Causes
-- This mode is in effect only due to pro-
gramming
options.
MODE
9 (MD09)
-- Night Ix_w Noise Active
Criteria
for Mode
--
This mode
is active when
the Night
Time Low Noise Option has been configured
and the time is
within the configured
time. Programming
a Night Low Noise
Start Time
(Configuration_OPTN--)LS.ST)
and
a Night
Low
Noise
End
Time
(Configuration
Mode_OPTN
-+LS.ND)
configures the option.
Action Taken -- The control will raise the head pressure set
point to reduce
the number
of condenser
fans on, thereby
reducing
file sound of the machine.
Additionally,
if file Night
Time Ix_w Sound
Capacity
Limit
((;bnfiguration_OPTN
-¢LS.LT)
has been configured,
the unit's capacity will be lim-
ited to the programmed
level.
Termination
-- This mode will terminate
once the Night Low
Noise End Time (LS.ND) has been reached.
Possible
Causes
-- This mode is in effect only due to pro-
gramming
options.