6. Press O
to Parmneter P3900. Press O
and use O
to change this value to 1. Press O
to accept.
7. The &'ive will finish standard programming.
Remove one
end of the jumper wire from terminal 8.
8. Press O
again and go to Ptu'ameter P0003. Press O
and use O
to change
this value to 3. Press O
to
accept.
9. Press O
to Parmneter P1210. Press O
and use O
to change this value to 6. Press O
to accept.
10. Press O
to Pmmneter
PI310.
Press O
and use O
to change this value to 10%. Press O
to accept.
11. Press the Function
O
key and then O"
The display
will read 0.00 Hz.
12.
13.
Replace the wire jumper in terminal 8.
The &'ive is now active.
Check
fan rotation
prior to testing.
If the fan is spinning
forward,
further
adjustment
is needed.
Fan should
sit still when
commanded
speed
is 0%. If the
fan is spinning forward slightly, press O
and _
to
Pmameter
P0761.
Press
am
and use a
to change
flais
value to 0.1. Press
Q
to'q_accept. Check1"the fan. If rotation
has stopped
no further
adjustment
is required.
If the fan
is still rotating
forward,
press_ O
and use O
to change
this value
to 0.2.
Press
O
to accept.
Repeat
as needed
until
the fan is holding
still or is just
bmely
moving
in
either
direction.
Do NOT
enter
a v_due
greater
than
0.5
for this
pm'ameter
without
th.'st
contacting
your
Cturier
representative.
Table 16 -- Low Ambient Temperature Controller Operator Panel
PANEL/BUTTON
FUNCTION
DESCRIPTION
Indicates Status
The LCD displays the settings currently used by the converter.
Start Converter
The Start Converter button is disabled by default. To enable this button set P0700 = 1.
O
O
Stop Converter
Press the Stop Converter button to cause the motor to come to a standstill at the selected
ramp down rate. Disabled by default, to enable set P0700 = 1.
Press the Stop Converter button twice (or hold) to cause the motor to coast to a standstill.
This function is always enabled.
O
Change Direction
Press the Change Direction button to change the direction of rotation of the motor.
Reverse is indicated by a minus (-) sign or a flashing decimal point. Disabled by default, to
enable set P0700 = 1.
O
Jog Motor
Press the Jog Motor button while the inverter has no output to cause the motor to start and
run at the preset jog frequency. The motor stops when the button is released. The Jog
Motor button is not enabled when the motor is running.
Functions
The Functions button can be used to view additional information.
Press and hold the but-
ton to display the following information
starting from any parameter during operation:
1. DC link voltage (indicated by d - units V).
2. Output current. (A)
3. Output frequency (Hz)
4. Output voltage (indicated by o - units V).
5. The value selected in P0005 (If P0005 is set to show any of the above [3, 4, or 5] then
this will not be shown when toggling through the menu).
Press the Functions button repeatedly to toggle through displayed values.
Jump Function
Press of the Fn button from any parameter (rXXXX or PXXXX) to immediately jump to
r0000, when another parameter can be changed, if required. Return to r0000 and press
the Functions button again to return.
Allows access to the parameters.
Access Parameters
O
Increase Value
Press the Increase Value button to increase the displayed value. To change the Frequency
O
Setpoint using the operator panel set P1000 = 1.
O
Decrease Value
Press the Decrease Value button to decrease the displayed value. To change the
Frequency Setpoint using the operating panel set P1000 = 1.
26