Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 71

Air-cooled liquid chillers
Table of Contents

Advertisement

PREFIX
CODE
P
SUFFIX
CODE
4O
41
42
43
73
74
78
79
8O
81
82
83
87
88
89
9O
91
ALARM
NUMBER
93
94
95
96
97
98
99
100
101
1 O2
1 O3
1 O4
1 O5
1 O6
1 O7
1 O8
1 O9
Table 39 -- Alarm Codes (cont)
ALARM
DESCRIPTION
Circuit
A -- Repeated
low
suction
temp overrides
Circuit
B -- Repeated
low
suction
temp overrides
Circuit
C -- Repeated
low
suction
temp overrides
Low entering
water
tempera-
ture in heating
Condenser
pump #1 default
Condenser
pump #2 default
Circuit
A High Discharge
Temperature
Circuit
B High Discharge
Temperature
Circuit
C High Discharge
Temperature
Circuit
A Low Economizer
Pressure
Circuit
B Low Economizer
Pressure
Circuit
C Low Economizer
Pressure
Circuit
A Slide Valve Control
Unverifiable
Circuit
B Slide Valve Control
Unverifiable
Circuit
C Slide Valve Control
Unverifiable
Cooler
flow switch set point
configuration
failure
Cooler
flow switch failure
REASON
FOR ALARM
Multiple
capacity
overrides
due to low satu-
rated suction
temperature
ACTION TAKEN
BY CONTROL
Circuit shut down
RESET
TYPE
Automatic
PROBABLE
CAUSE
Inaccurate
transducer,
faulty EXV,
low refrigerant
charge,
plugged
or restricted
liquid line filter drier.
Not supported
--
Configuration
error
None
Circuit
shut down
Circuit
shut down
Discharge
gas tempera-
ture is higher
than 212 F
for more than 90 seconds
Alarm
tripped
Manual
Manual
Manual
Manual
The economizer pressure
is below the suction pres-
sure more than 14.5 psi
for more than 10 seconds
If 100% load current
is
less than 1.3 times of 30%
load current,
or 30% load
current
is greater
than
0.78 times of expected
100% load current
Faulty transducer/high
pressure
switch,
low/
restricted
condenser
flow
Faulty transducer,
faulty main base board,
faulty wiring,
closed
suction
service valve,
faulty
EXV
CPM board
detects cur-
rent unbalance
greater
than 65% for more than
1 second
Slide valve stuck,
inac-
curate
initial current
reading
--
None
Manual
Configuration
error
Flow switch
open
Unit shut down
Manual
if unit
Faulty flow switch,
low
is running,
cooler flow, faulty
automatic
wiring,
faulty cooler
otherwise
pump, faulty main base
board
Sr
nn
110
Service
maintenance
alert
Field programmed
None
Manual
Maintenance
required
Number
# nn
elapsed
time has expired
for maintenance
time
A1, B1, Cl
01
111-01,
Compressor
Motor tempera-
Compressor
temperature
Circuit
shut down
Manual
Motor cooling solenoid
112-01,
ture too high
higher than 232 F for
or economizer
113-01
more than 90 seconds
EXV failure,
faulty
CPM board, low
refrigerant
charge
02
111-02,
Compressor
Motor tempera-
Compressor
temperature
Circuit
shut down
Manual
Faulty thermistor,
faulty
112-02,
ture out of range
reading out of the range of
wiring,
faulty CPM
113-02
-40
F to 245 F
board
03
111-03,
Compressor
High pressure
HPS input on CPM board
Circuit
shut down
Manual
Loss of condenser
air
112-03,
switch
protection
open
flow, operation
beyond
113-03
compressor
envelope,
faulty
high pressure
switch,
faulty wiring,
faulty CPM board
04
111-04,
Compressor
Over current
CPM board detects
high
Circuit
shut down
Manual
Operating
beyond
112-04,
motor current
compared
chiller
envelope,
incor-
113-04
with MTA setting
rect configuration
05
111-05,
Compressor
Locked
rotor
CPM board detects
locked
Circuit
shut down
Manual
Compressor
motor fail-
112-05,
rotor current
compared
ure, unloader
slide
113-05
with MTA setting
valve failure, compres-
sor mechanical
failure
Circuit shut down
Manual
Blown fuse, wiring
error, loose terminals
06
111-06,
112-06,
113-06
07
111-07,
112-07,
113-07
08
111-08,
112-08,
113-08
09
111-09,
112-09,
113-09
Compressor
Phase loss L1
Compressor
Phase loss L2
Compressor
Phase loss L3
Compressor Low current
CPM detects motor cur-
Circuit shut down
Manual
Power supply discon-
alarm
rent less than a certain
nected, blown fuse,
percentage of the MTA
wiring error, contact
setting
deenergized, faulty
current toroid.
--
Must Trip Amps
--
Outdoor
Air Temperature
--
Saturated
Suction
Temperature
--
Underwriters'
Laboratories
LEGEND
CON
i
Carrier Comfort Network®
MTA
CPM
-- Compressor Protection Module
OAT
EMM
-- Energy Management Module
SST
EXV
-- Electronic Expansion Valve
UL
MOP
-- Maximum Operating Pressure
*NRCP2
is the Energy
Management
Board.
71