Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 40

Air-cooled liquid chillers
Table of Contents

Advertisement

EXTERNALLY
POWERED
(4 to 20 mA Controlled)
-- The
Energy
Management
Module
is required
for 4 to 20 mA
demand
limit control.
To configure
demand
limit for 4 to
20 mA control three parameters
must be configured.
They are:
Demand Limit Select (Configuration
_RSET--+DMDC),
mA
for 100% Demand
Limit (Configuration---)RSET-cDMMX)
and mA for 0% Demand
Limit
(Configuration---)RSET---)
DMZE).
In the following
example, a 4 mA sigmd is Demand
Limit 100% and a 20 mA Demand Limit signal is 0%. The 4 to
20 mA signal is connected
to TB6-1 and TB6-2. The demand
limit is a linear intelpolation
between
the two values entered.
See Table 26 and Fig. 21.
Ctue should be taken when interfacing with other control
systems due to possible power supply differences such as a
full wave bridge versus a half wave rectification. Connec-
tion of control devices with different power supplies may
result in pemmnent damage.
Col@)rtLink
TM
controls
incorporate power supplies wifll half wave rectification. A
signal isolation device should be utilized if the signal gen-
erator incorporates a full wave bridge rectifiel:
In Fig. 21, if the machine
receives
a 12 mA signal, the
machine controls will limit the capacity to 50%.
CCN LOADSHED
CONTROLLED
-- To configure Demand
Limit for CCN
Ix)adshed
control
the unit Operating
Type
Control
must
be
in CCN
control,
(Operating
Modes---)
SLCT---)SP.SE=2)
and be controlled
by a Chillervisor
module.
The Chillervisor
module can force the demand
limit variable
and directly control the capacity of the machine.
Additionally.
the unit's set point will be artificially lowered to force the chill-
er to load to the demand limit v:due.
Remote Alarm and Alert Relays -- The 30XA chill-
er can be equipped with a remote alert and remote alarm
annunciator contacts. Both relays connected to these contacts
must be rated for a maximum power draw of 10 va setded,
25 va inrush tit 24 volts. The almm relay, indicating that the
complete unit has been shut down can be connected to TB5-12
and TB5-13. Refer to unit wiring diagrams. For an alert relay,
indicating that tit least 1 circuit is off due to the alert, a field-
supplied and insttdled relay must be connected between MBB-
J3-CH25-3 and TB5-13.
Table 26 -- Externally Powered Demand Limit Configuration
MODE
KEYPAD
ENTRY
DISPLAY
ITEM EXPANSION
COMMENT
CONFIGURATION
[]
DISP
]
UNIT
]
SERV
]
OPTN
]
RSET
Reset Cool and Heat Tmp
]
CRST
]
HRST
]
DMDC
DemandLimit Select
]
0
None
]
0
None
Flashing
to indicateEdit mode.
May require
Password
]
2
4-20 mA
Input
Useup arrowsto
change
value to 2.
]
2
Accepts
the change.
DMDC
]
DMMX
mA for 100%DemandLimit
[]
o
]
0
Flashing
to indicate
Edit mode
]
4.0
Use up arrowsto changethe valueto 4.
DMMX
]
DMZE
mA for 0% DemandLimit
[]
o
]
0
Flashing
to indicate
Edit mode
]
20.0
Useup arrowsto changevalue to 20.
]
DMZE
NOTE: Bold values indicate sub-mode level.