Setpoint Control - Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

Table 18-
Alarm Messages
FAULT
A0501
Current Limit
A0502
Overvoltage
Limit
POSSIBLE CAUSES
• Motor power does not correspond
to the
drive power
• Motor leads are too short
• Ground fault
• Mains supply too high
• Load regenerative
• Ramp-down
time tee short
A0503
• Mains supply too low
Undervoltage
Limit
• Short mains interruption
A0504
Warning level of inverter heat-sink temperature
1. Check if ambient temperature
is within specified
limits
Drive
(P0614) is exceeded,
resulting
in pulse fre-
2. Check load conditions and duty cycle
Overtemperature
quency reduction and/or output frequency
3. Check if fan is turning when drive is running
reduction
(depending
on parameters
set
(P0610)
A0505
Warning level is exceeded;
current will be
Check if duty cycle is within specified
limits
Drive 12t
reduced
if parameters
set (P0610 = 1)
A0506
Heatsink temperature
and thermal junction
Check if duty cycle is within specified
limits
Drive Duty Cycle
model are outside of allowable range
A0511
Motor overloaded
Check the following:
Motor
1. P0611 (motor 12ttime constant) should be set to appropriate
value
Overtemperature
12t
2. P0614 (motor 12t overload warning level) should be set to suitable level
3. Are long periods of operation
at low speed occurring
4. Check that boost settings are not too high
A0541
Motor data identification
(P1910) selected or
Wait until motor identification
is finished
Motor
Data
running
Identification
Active
A0600
Software
error
RTOS Overrun
Warnin_
LEGEND
i2t -- Current Squared Time
TROUBLESHOOTING
1. Check whether the motor power corresponds
to the drive power
2. Check that the cable length limits have not been exceeded
3. Check motor cable and motor for short-circuits
and ground faults
4. Check whether the motor parameters
correspond with the motor being used
5. Check the stator resistance
6. Increase the ramp-up-time
7. Reduce the boost
8. Check whether the motor is obstructed or overloaded
1. Check that mains supply voltage is within allowable range
2. Increase ramp down times
NOTE: If the vdc-max controller
is active, ramp-down times will be automatically
increased
Check main supply voltage (P0210)
Machine
Control
Methods
-- Tinge
variables control
how the machine operates.
One vmiable controls the machine
On-Off function. The second controls the set point operation.
The third variable controls the Heat-Cool
operation.
Table 19
illustrates how the control method and cooling set point select
variables dilect file operation
of the chiller and the set point to
which it controls. Table 19 _fl s o provides the On/Off state of the
machine for the given combinations.
Machine On/Off control is determined
by the configuration
of the Operating
Type
Control
(Operating
Modes--+SLCT
_OPER).
Options to control the machine locally via a switch,
from a local Time Schedule,
or via a Carrier Comfort Network
command
are offered.
SWITCH
CONTROL
--In
this Operating
Type Control, the
Enable/Off/Remote
Contact switch controls the machine locally.
All models are factory configured with OPER=O (Switch Con-
trol). With the OPER set to 0, simply switching the Enable/Off/
Remote Contact switch to file Enable or Remote Contact posi-
tion (external contacts closed) will put the chiller in tin occupied
state. The unit Occupied
Status (Run Status-+VIEW_OCC)
will change fiom NO to YES. The Status Unit Control Type
(Run Status--_VIEW_CTRL)
will change fiom 0 (Ix_cal Off)
when the switch is Off to 1 (Ix_cal On) when in the Enable posi-
tion or Remote Contact position with external contacts closed.
TIME SCHEDULE-
In this Operating
Type Control,
the
machine
operates under a local schedule programmed
by the
user as long as the Enable/Off/Remote
Contact switch is in the
Enable or Remote Contact position (external
contacts closed).
To operate
under
this Operating
Type
Control,
Operating
Modes-+SLCT
must be set to OPER=I.
Two Internal Time
Schedules
are available.
Time Schedule
1 (Time
Clock--_
SCH1)
is used for single set point On-Off control. Time Sched-
ule 2 (Time Clock_SCH2)
is used for dual set point On-Off
and Occupied-Unoccupied
set point control. The control will
use the operating
schedules
as defined under the Time Clock
mode in the Navigato( r_'_display module.
CCN Global Time Schedule
-- A CCN Global Schedule
can
be utilized. The schedule
number
can be set anywhere
from
65 to 99 for operation
under
a CCN
glob_d schedule.
The
30XA
chillers
can be configmed
to follow a CCN
Global
Time Schedule
broadcast
by another
system
element.
The
IM
ComfortVIEW
Network
Manager's
Configure
and Modily
commands
or the Selwice Tool's Modify/Nmnes
function must
be used to change the number
of the Occupancy
Equipment
Part
Table
Name
(OCCIP01E)
to the
Global
Schedule
Numbel:
The Schedule
Number
can be set from 65 to 99
(OCC 1P65E to OCC 1P99E).
The Occupancy
Supervisory
Part table name (OCCIPOI
S)
number must be changed to configure
the unit to broadcast
a
Global Time Schedule.
The Schedule
Number can be set from
65 to 99 (OCCIP65S
to OCCItX)9S).
When OCCIPxxS
is set
to a v_due greater than 64, an occupancy
flag is broadcast over
the CCN every time it transitions
from occupied to unoccupied
or vice-versa.
By configuring
their appropriate
Time Schedule
decisions to fl-_esame numbel, other devices on the network can
follow this same
schedule.
The Enable/Off/Remote
Contact
must be in the Enable position or Remote Contact position with
flae contacts
closed
for the unit to operate.
The Status
Unit
Control Type (Run Status--cVIEW--cSTAT)
will be 0 (Ix_cal
Off) when the switch is Off. The Status Unit Control Type will
be 2 (CCN) when the Enable/Off/Remote
Contact switch input
is On.
CCN CONTROL
-- An external CCN device such as Chill-
ervisor controls
the On/Off
state of the machine.
This CCN
device forces the variable CHIL_S_S
between
Start/Stop
to
control the chillel: The Status Unit Control Type (Run Status--€
VIEWS'TAT)
will be 0 (Loc_d Off) when the Enable/Off/
Remote Contact switch is Off. The Status Unit Control
Type
will be 2 (CCN) when the Enable/Off/Remote
Contact switch
input is Closed and the CHIL_S_S
variable is Stop or Start.
29