Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 25

Air-cooled liquid chillers
Table of Contents

Advertisement

Fig. 12-
Low Ambient Temperature
Controller
Changing
Single Digits in Parameter
Values
--
For chang-
ing the parametel_
value rapidly, the single digits of the display
can be changed by performing
the following actions:
Ensure the operator panel is in the ptuameter
v_due chang-
ing level as described
in the Changing
Parametel:s
with the
Operator Panel section.
1. Press Q
(function
button),
which
causes
the farthest
right digit to blink.
Change the value of this digit by pressing
O
or O
"
2.
Pressing O
(function
button)
again to cause
3.
tile next
digit to blink.
4. Perforln steps 2 to 4 until tile required value is displayed.
5. Press O
(parameter
button) to exit the parmneter
v_flue
changing level.
NOTE: The lunction button may also be used to acknowledge
a fault condition.
OuickCommissioning
(P0010=I)
--
It is important
that
parameter P0010 is used for commissioning
and P0003 is used
to select the number of parameters
to be accessed.
The P0010
parameter allows a group of parameters
to be selected that will
enable quick commissioning.
Parametel_
such as motor set-
tings and ramp settings are included.
At the end of the quick
commissioning
sequences,
P3900
should be selected, which,
when set to 1, will carry out the necessary
motor calculations
and clear all other parameters
(not included
in P0010=I
to the
default settings. This will only occur in Quick Commissioning
mode. See Fig. 14.
Reset to FactoLy Default -- To reset all parameters
to the fac-
tory default settings, the following
parameters
should be set as
follows:
1. Jumpers
must be in place from termimds
2 and 4 and 5
and 8 (5 and 9 for 575v &'ives only).
2. Remove the keypad (pull out from top) and verify that
DIP switch 1 is OFF and 2 is ON. Replace keypad.
3. Power up the drive. Press Parameter
t
key. Press
to Parameter
P0010.
4. Press Q,
then O
to change the 0 to a 1. Pless Q
again to accept the change.
5. Press _
to Parmneter
P0311.
Press _
and press
to change
to
6-pole
motors
this
value
1140 for
or 850 for units with 8-pole motors. Press _
to accept.
CHANGING
P0004 -- PARAMETER
FILTER
FUNCTION
I
StEP
II
RESULT°N
DISPLAY
1
Press _
to access parameters
2
Press O
until P0004 is displayed
Press O
value level
to access the parameter
4
Press _
or _
to the required
value
5
Press A
to confirm and store the
value
6
Only the command parameters are
visible to the user.
CHANGING P0719 AN INDEXED PARAMETER
SELECTION OF COMMAND/SETPOINT
SOURCE
I
I
STEP
Jl
°" I
1
Press O
to access parameters
2
Press 0
until P0719 is displayed
3
Press 0
to access the parameter
value level
Press 0
to display current set value
5
Press _
or _
to the required
value
6
Press A
to conform and store the
value
7
Press 0
until rO000 is displayed
8
Press Q
to return the display to the
standard drive display (as defined by
the customer)
Fig. 13-
Changing
Parameters
with the Operator
Panel
25