Energy Management Module (Emm); Local Equipment Network; Board Addresses; Control Module Communication - Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Table of Contents

Advertisement

©
INPUT
4-20 mA Demand
Limit
4-20 mA Temperature
Reset]Cooling
Setpoint
Demand
Limit SW2
Ice Done
Occupancy
Override
Remote Lockout Switch
SPT
OUTPUT
% Total Capacity
RUN R
SHD R
NOTE: Used on 30XA080-500.
Fig. 6 -- Energy Management Module
Table 10 -- Energy Management Module (EMM) Inputs and Outputs
DESCRIPTION
I/O TYPE
I/O POINT NAME
CONNECTION
POINT
4-20 mA Demand Limit
4-20 mA
INPUTS-_GEN.I-_DMND
EMM-J7B-CH6
4-20 mA Temperature
Reset/
4-20 mA
INPUT$-_GEN.I-_RSET
EMM-J7A-CH5
Cooling Set point
Demand Limit Step 2
Switch Input
INPUT$-_GEN.I-_DLS2
EMM-J4-CH9
Ice Done Switch
Switch Input
INPUTS-_GEN.I-MCE.D
EMM-J4-CH 11A
Occupied
Schedule Override
Switch Input
INPUTS-_GEN.I-_OCCS
EMM-J4-CH8
Chiller Lockout
Switch Input
INPUT$-_GEN.I-_RLOC
EMM-J4-CH 10
Space Temperature
Thermistor
10k Thermistor
TEMPERATURE-_UNIT-_$PT
EMM-J6-CH2
DESCRIPTION
I/O TYPE
I/O POINT NAME
CONNECTION
POINT
0-10 vdc
OUTPUTS-+GEN.O-+CATO
EMM-J8-CH7
Run Relay
Relay
OUTPUT$-_GEN.O-_RUN
EMM-J3-CH25
Shutdown
Relay
Relay
OUTPUTS-_GEN.O-_SHUT
EMM-J3-CH24
Local
Equipment
Network
--Information
is trans-
mitted between modules
via a 3-wire cornmunication
bus or
LEN (Local Equipment
Network).
External
connection
to the
LEN bus is made fit TB3.
Board Addresses
--
All
bofu'ds
(except
the Main
Base
Board,
Energy
Management
Module
Board,
find Compressor
Protection
Module
Bornd)
have
8-position
DIP
switches.
Addresses
for all boards
ate listed
with the Input!Output
Tables
for each board,
Control
Module
Communication
RED LED -- Proper operation
of the control boards can be
visually
checked
by looking
at file red status LEDs (ligltt-
emitting
diodes).
When
operating
correctly,
the red status
LEDs will blink in unison at a rate of once every 2 seconds. If
the red LEDs are not blink in unison, verify that correct power
is being supplied
to all modules.
Be sure that the Main Base
Board (MBB) is supplied with the cunent
soflwme.
If neces-
sary, teload
current
soflwate.
If tlte problem
still persists,
replace the MBB. A red LED that is lit continuously
or blink-
ing at a rate of once per second or faster indicates that the bomd
should be replaced.
GREEN
LED -- All boards
have a green LEN (SIO) LED
which should be blinking whenever
power is on. If the LEDs
are not blinking
as described
check
LEN
connections
for
potential
communication
errors fit the board connectot_.
See
Input/Output
Table 2, and 4-10 for LEN Connector
designa-
tions.
A 3-wire
bus accomplishes
communication
between
modules. These 3 wires tun in parallel from module to module.
The J9A connector
on the MBB provides
communication
di-
rectly to the Navigator :m display module.
YELLOW
LED-
Tlte MBB
has one
yellow
LED.
The
Cmtier
Comfort
Network®
(CCN)
LED will blink
during
times of network communication.
14