Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 21

Air-cooled liquid chillers
Table of Contents

Advertisement

Override
#13: Minimum
On/Off
and Off/On Time Delay --
Whenever
a capacity change has been made, the control will
remain at this capacity stage for the next 90 seconds.
During
this time, no capacity
control algorithm
cCdculations will be
made.
If the capacity
step is a compressor,
an additional
90-second
delay is added to the previous hold time (see Over-
ride #227. This override allows the system to stabilize before
another capacity stage is added or removed.
If a condition of a
higher priority override occurs, the higher priolity override will
take precedence.
Operating
Mode 10 (MDI 0) will be in effect.
Override
#14: Slow Change Override
--
This override pre-
vents compressor
stage changes when the leaving temperature
is close to the control point and slowly moving
towards
the
control point.
Override
#15: System
Manager
Capacity
Control
--
If
a
Chillervisor
module is controlling
the unit and the Chillervisor
module
is controlling
multiple
chillers, the unit will increase
capacity to attempt to load to the demand limited v_due.
Override #16: Circuit A High Pressme Override
Override #17: Circuit B High Pressure Override
Override #18: Circuit C High Pressure Override
-- This over-
ride attempts to avoid a high pressure failure. The algorithm
is
run evely 4 seconds. If the Saturated Condensing
Temperature
for the circuit is above the High Pressure Threshold
(Configu-
ration--+ SERV--+HP.TH)
then the position of slide valve will
be unloaded.
Override
#19: Standby
Mode -- This override algorithm
will
not allow a compressor
to run if the unit is in Standby mode,
(Run Status--)VIEW--_HC.ST=2).
Override
#22: Minimum
On Time Delay
--
In addition
to
Override
#13 Minimum
On/Off and Off/On Time Delay, for
compressor
capacity
changes,
an additional
90-second
delay
will be added to Override
#13 delay. No compressor
will be
deenelgized
until 3 minutes
have elapsed
since the last com-
pressor has been turned ON. When this override is active, the
capacity control _dgorithm calculations
will be perf(mned,
but
no capacity reduction
will be made until the timer has expired.
A control with higher precedence
will override the Minimum
On Time Delay.
Override
#23: Circuit A Low Saturated
Suction
Temperature
in Cooling
Override
#24: Circuit B Low Saturated
Suction
Temperature
in Cooling
Override
#25: Circuit
C Low Saturated
Suction
Tempera-
ture in Cooling
-- If the circuit is operating in an gu'ea close to
the operational
limit of the compressol:
the circuit capacity will
remain at the same point or unload to raise the saturated suction
temperatme.
This _dgorithm will be active if at least 1 comples-
sot in the circuit is on and one of the following conditions
is tree:
1. Saturated
Suction
Temperature
is less than the Brine
Fleeze Setpoint (Configuration
--_;ERV--cLOSP)
- 6 ° F
(3.3 ° C).
2. Saturated
Suction
Telnperature
is less than the Brine
Fleeze
Setpoint
(Configuration--cSERV--cLOSP)
and
the circuit approach
(Leaving Water Temperature
- Satu-
rated Suction Temperature)
is greater than 15 ° F (8.3 ° C)
and the Circuit Supoheat
(Discharge
Gas Temperatme
-
Saturated
Discharge
Temperatme)
is greater than 25° F
(13.9 ° C).
NOTE:
The freeze set point is 34 F (1.1 C) for fresh
water systems (Configuration
---_S'ERV---_FLUD=I).
The
freeze set point is Brine Freeze Set Point (Conjqguration
--+SERV--+LOSP),
for
Medium
Temperature
Brine
systems (Configuration
---_SERV---_FLUD=2).
If any of these conditions
gue met, the appropriate
operating
mode, 21 (Circuit A), 22 (Circuit B) or 23 (Circuit C) will be in
effect.
Override
#26: Circuit A High Discharge
Gas Override
Override
#27: Circuit B High Discharge
Gas Override
Override
#28: Circuit C High Discharge
Gas Override
--
When the temperature
is above the limit curve minus
2 ° F
(1.1 ° C) increase in capacity will not be allowed. This ovemde
will remain active until the DG_" goes below the limit curve by
-3 ° F (-1.7 ° C).
OvelTide #34: Circuit A Low Refi'igerant
Charge
Override
#35: Circuit B Low Refiigerant
Charge
Override
#36: Circuit C Low Refrigerant
Charge -- The ca-
pacity override attempts
to protect the compressor
from start-
ing with no refiigemnt
in the circuit. This algorithm runs only
when the circuit is not operational
(no compressors
are ON).
There are several criteria that will enable this override:
1. The saturated suction temperature
or saturated dischmge
temperature
is less than -13 F (-10.6 C).
2. All of these conditions
must be true:
a.
The
saturated
suction
temperature
or saturated
discharge
temperature
is less than leaving
water
temperature
by more than 5.4 ° F (3.0 ° C).
b.
Saturated
suction
temperature
or saturated
dis-
charge temperature
is less than 41 F (5 C).
c.
Outdoor
air temperature
is less than 32 F (0 ° C).
d.
Saturated
suction temperature or saturated
discharge
temperature
is less than the outdoor air temperature
by more than 5.4 ° F (3.0 ° C).
3. All of these conditions
must be true:
a. The saturated
suction temperature or saturated
discharge temperature
is less than leaving water
temperature by more than 5.4° F (3.0° C).
b. Saturated
suction temperature
or saturated
dis-
charge temperature is less than 41 F (5 C).
c. Saturated
suction temperature
or saturated
dis-
charge temperature
is less than the brine freeze
point (Configuration--+SERV--+LOSP)
by more
than 6° F (3.3° C).
NOTE: The freeze set point is 34 F (1.1 C)
for fresh water systems
(Configuration---)SERV
--+FLUD=I). The freeze set point is brine freeze
set point
(Configuration--_SERV--_LOSP),
for
medium temperature
brine systems (Configura-
tion --_SER V--)FLUD=2 ).
All of these conditions must be true:
a.
The
saturated
suction
temperature
or saturated
discharge
temperature
is less than leaving
water
temperature
by more than 5.4 ° F (3.0 ° C).
b.
Saturated
suction temperature
or saturated discharge
temperature
is less than 41 F (5 C).
c.
Saturated
suction temperature
or saturated discharge
temperature
is less than the outdoor air temperature
by more than 9 ° F (5 ° C).
If any of these conditions
1,2, 3 or 4 are met, the appropri-
ate operating
mode,
21 (Circuit
A), 22 (Circuit
B) or 23
(Circuit C) will be in effect.
Override
#41 : Circuit A High Current Override
Override
#42: Circuit B High Current
Override
Override
#43: Circuit C High Current
Override
This override attempts
to avoid an overcurrent
failure. The
_dgorithm is run every 4 seconds. If the compressor
current is
greater than 79% of must trip amps (MTA) but less than 85%
MTA then the capacity will be held at current capacity. If the
compressor
current is greater
than 85% MTA then capacity
will be reduced
by repositioning
the slide valve
until the
current
is less than 85% MTA
(Configuration--cUNIT--€
MTA.X).
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents