Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 83

Air-cooled liquid chillers
Table of Contents

Advertisement

Example -- Test the condenser tim AI (see Table 43).
Power must be applied to the unit. Enable/Off/Remote
Contact switch must be in the OFF position.
Test the condenser fans, cooler pump(s) and alarm relay by
changing the item values fiom OFF to ON. These discrete
outputs me then turned off if there is no keypad activity for
10 minutes. Test the compressor and minimum load valve sole-
noid (if installed) outputs in a similar mannel: Tile minimum
load valve solenoids will be turned off if there is no keypad
activity for 10 minutes. Compressors will stay on until the
operator turns them off. The Service Test mode will remain
enabled
for as long as them
is one or more
compressors
running.
All safeties am monitored
during this test and will
turn a compressor,
cimuit or the machine off if required. Any
other mode or sub-mode
can be accessed,
viewed, or changed
during the Manual
Control mode only. Tile STAT item (Run
Status --)VIEW) will display "0" as long as the Service mode is
enabled. Tile TEST sub-mode
value must be changed back to
OFF befom the chiller can be switched
to Enable or Remote
contact for normal operation.
NOTE:
Them may be up to a one-minute
delay before
the
selected item is energized.
Table 43 -- Testing Circuit A Oil Solenoid
MODE
SUB-MODE
KEYPAD
ITEM
DISPLAY
VALUE
DESCRIPTION
COMMENT
(Red LED)
ENTRY
EXPANSION
(Units)
SERVICE TEST
[]
Service Test Mode
TEST
[]
Manual Sequence
QUIC
[]
Q.REQ
PASS WORD
Password may be required
]
0111
[]
Each []
will lock in the next
]
digit. If 0111 is not the password,
use the arrow keys to change the
[]
_assword digit and press []
]
when correct.
]
Q.REQ
Returns to the original field
]
OFF
]
OFF
OFF will flash
The Enable/Off/Remote
Contact
]
ON
switch must be in the OFF
_osition.
Q.REQ
]
EXV.A
]
Press 15 times.
]
OLG.A
Oil Solenoid cir.A
]
OFF
]
OFF
OFF will flash
[]
oN
]
ON
OLS.A will turn on.
]
ON
1 will flash
]
OFF
]
OFF
OLS.A will turn off.
LEGEND FOR FIG. 42-44
ALM
-- Isolation
CB
-- Circuit Breaker
CPM
-- Compressor
Protection Module
CWFS
-- Chilled Water Flow Switch
EMM
-- Energy Management Module
EXV
-- Electronic Expansion Valve
FlOP
-- Factory-Installed
Option
HTR
-- Heater
ISO
--
MBB
--
MLV
--
MM
--
PMP
--
SGT
--
TB
--
Isolation
Main Base Board
Minimum Load Value
Low Ambient Temperature Head Pressure Control
Pump
Saturated Gas Temperature
Terminal Block
83