Carrier AquaForce 30XA Series Installation Instructions Manual

Air-cooled liquid chillers
Hide thumbs Also See for AquaForce 30XA Series:

Advertisement

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . .1,2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-160
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 - Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 - Place, Mount and Rig Unit . . . . . . . . . . . . . . . 2
Drain Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . 108
Step 4 - Fill the Chilled Water Loop . . . . . . . . . . . . . . 129
Step 5 - Make Electrical Connections. . . . . . . . . . . . 133
COMMUNICATION BUS WIRING
Step 6 - Install Accessories . . . . . . . . . . . . . . . . . . . . . 158
• REMOTE SENSOR (CLOSED LOOP)
Step 7 - Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Step 8 - Refrigerant Charging . . . . . . . . . . . . . . . . . . . 159
Step 9 - Optional BACnet Communication
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300110-01
Installation Instructions
Page
®
Printed in U.S.A.
Form 30XA-19SI Rev. A
Air-Cooled Liquid Chillers

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be hazard-
ous due to system pressures, electrical components, and equip-
ment location. Only trained, qualified installers and service me-
chanics should install, start up, and service this equipment.
When working on the equipment, observe precautions in the liter-
ature, and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky equipment.
WARNING
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation. There may be
more than one disconnect switch. Tag all disconnect locations
to alert others not to restore power until work is completed.
IMPORTANT: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with these instructions may cause
radio interference. It has been tested and found to comply
with the limits of a Class A computing device as defined
by FCC (Federal Communications Commission, U.S.A.)
regulations, Subpart J of Part 15, which are designed to
provide reasonable protection against such interference
when operated in a commercial environment.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gage for how
much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal inju-
ry or death.
Pg 1
AquaForce
30XA080-501
2-2020
Replaces: 30XA-18SI
®

Advertisement

Table of Contents
loading

Summary of Contents for Carrier AquaForce 30XA Series

  • Page 1: Table Of Contents

    • FIELD POWER CONNECTIONS • POWER WIRING WARNING • FIELD CONTROL POWER CONNECTIONS DO NOT USE TORCH to remove any component. System • CARRIER COMFORT NETWORK ® contains oil and refrigerant under pressure. COMMUNICATION BUS WIRING • NON-CCN COMMUNICATION WIRING To remove a component, wear protective gloves and goggles •...
  • Page 2: Introduction

    See Tables 1A and 1B. Mounting cal Carrier representative. holes are provided for securing the unit to the pad, mounting rail or vibration isolation springs. Bolt the unit securely to pad or rails.
  • Page 3 Packaging/Security Options 0 – Coil Face Shipping Protection (CFSP), Skid 30XA – AquaForce® Air-Cooled Chiller 1 – CFSP, Skid, Top Crate, Bag 3 – CFSP, Coil Trim Panels Design Series 4 – CFSP, Skid, Coil Trim Panels Unit Sizes* 5 – CFSP, Skid, Top Crate, Bag, Coil Trim Panels 7 –...
  • Page 4 a30-5189...
  • Page 5 a30-5190 a30-4403...
  • Page 6 a30-5191 a30-4403...
  • Page 7 a30-5530...
  • Page 8 a30-5192...
  • Page 9 a30-5703 a30-5193...
  • Page 10 a30-5194...
  • Page 11 a30-5195...
  • Page 12 a30-5703 a30-5196...
  • Page 13 a30-5197...
  • Page 14 a30-5531...
  • Page 15 a30-5532...
  • Page 16 a30-5198...
  • Page 17 a30-5199 a30-4404...
  • Page 18 a30-5200...
  • Page 19 a30-5204...
  • Page 20 a30-4407...
  • Page 22 a30-5205...
  • Page 23 a30-4407...
  • Page 24 a30-5208...
  • Page 25 a30-5480...
  • Page 26 A30-...
  • Page 27 a30-5206...
  • Page 28 a30-5207...
  • Page 29 a30-4408...
  • Page 30 a30-4174...
  • Page 31 a30-4174...
  • Page 32 a30-5482...
  • Page 33 a30-5483 A30-5483...
  • Page 34 a30-5210...
  • Page 35 a30-5211...
  • Page 36 a30-4409...
  • Page 37 a30-4176...
  • Page 38 a30-5212...
  • Page 39 a30-5484 a30-5484...
  • Page 40 a30-5485...
  • Page 41 a30-5214...
  • Page 42 a30-5215...
  • Page 43 a30-4177...
  • Page 44 a30-4178...
  • Page 45 a30-5216...
  • Page 46 a30-5486 a30-5486...
  • Page 47 a30-5487...
  • Page 48 a30-5488...
  • Page 49 a30-5489...
  • Page 50 a30-5218...
  • Page 51 a30-5217...
  • Page 52 a30-4410...
  • Page 53 a30-4180...
  • Page 54 a30-5220...
  • Page 55 a30-5490...
  • Page 56 a30-5491...
  • Page 57 a30-51222...
  • Page 58 a30-5221...
  • Page 59 a30-4181...
  • Page 60 a30-4182...
  • Page 61 a30-5224...
  • Page 62 a30-5226...
  • Page 63 a30-5225...
  • Page 64 a30-4181...
  • Page 65 a30-4182...
  • Page 66 a30-5227...
  • Page 67 a30-5595...
  • Page 68 a30-5596small...
  • Page 70 a30-4183...
  • Page 71 a30-4183...
  • Page 72 a30-4184...
  • Page 73 a30-4184...
  • Page 74 a30-4183...
  • Page 75 a30-4183...
  • Page 76 a30-4183...
  • Page 77 a30-4184...
  • Page 78 a30-4184...
  • Page 79 a30-5597...
  • Page 80 a30-5598...
  • Page 81 a30-5599...
  • Page 82 a30-5600...
  • Page 83 a30-5601...
  • Page 84 a30-5602...
  • Page 85 UNITS WITHOUT PUMPS — ENGLISH MOUNTING WEIGHT (lb) 30XA MCHX CONDENSER COILS UNIT SIZE Total 1947 1673 1670 1943 7234 1989 1709 1706 1985 7391 MOUNTING WEIGHT (lb) MCHX CONDENSER COILS 30XA UNIT SIZE Total 1201 2043 1983 1199 8127 1219 2074 2013...
  • Page 86 UNITS WITHOUT PUMPS — SI MOUNTING WEIGHT (kg) 30XA MCHX CONDENSER COILS UNIT SIZE Total 3281 3353 MOUNTING WEIGHT (kg) MCHX CONDENSER COILS 30XA UNIT SIZE Total 3686 3742 3786 3843 3848 3955 3911 1010 4006 MOUNTING WEIGHT (kg) MCHX CONDENSER COILS 30XA UNIT SIZE Total...
  • Page 87 30XA080,082 30XA220-302 COOLER SIDE COOLER SIDE a30-4419 a30-4423 COMPRESSOR SIDE COMPRESSOR SIDE 30XA090-122 30XA325-352 COOLER SIDE COOLER SIDE a30-4424 a30-4420 COMPRESSOR SIDE COMPRESSOR SIDE 30XA400-501A 30XA140-162 COOLER SIDE COOLER SIDE a30-4425 a30-4421 COMPRESSOR SIDE COMPRESSOR SIDE 30XA501B 30XA180-202 COOLER SIDE COOLER SIDE a30-4422 a30-4419...
  • Page 88 SINGLE PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) MCHX CONDENSERS 30XA UNIT SIZE Total 1201 2754 1087 1944 1199 9085 1217 2791 1102 1970 1215 9209 1226 2814 1123 1995 1224 9306 1242 2851 1138 2022 1240 9430 1239 2855 1145 2027 1229...
  • Page 89 DUAL PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) MCHX CONDENSERS 30XA UNIT SIZE Total 1201 2962 1176 1944 1199 9,382 1217 3001 1192 1970 1215 9,506 1226 3022 1212 1995 1224 9,603 1242 3061 1228 2021 1240 9,727 1239 3064 1234 2027 1229...
  • Page 90 UNITS WITHOUT PUMPS — ENGLISH MOUNTING WEIGHT (lb) — Al/Cu* 30XA UNIT SIZE Total 2059 1785 1778 2051 7674 2101 1822 1814 2093 7831 MOUNTING WEIGHT (lb) — Al/Cu* 30XA UNIT SIZE Total 1273 2188 1023 2127 1271 8704 1291 2219 1038 2157...
  • Page 91 UNITS WITHOUT PUMPS — SI MOUNTING WEIGHT (kg) — Al/Cu* 30XA UNIT SIZE Total 3481 3552 MOUNTING WEIGHT (kg) — Al/Cu* 30XA UNIT SIZE Total 3948 1007 4004 1018 4051 1032 1004 4107 1036 1008 4115 1063 1034 4222 1053 1023 4181 1077...
  • Page 92 30XA080,082 30XA220-302 COOLER SIDE COOLER SIDE a30-4419 a30-4423 COMPRESSOR SIDE COMPRESSOR SIDE 30XA090-122 30XA325-352 COOLER SIDE COOLER SIDE a30-4424 a30-4420 COMPRESSOR SIDE COMPRESSOR SIDE 30XA400-501A 30XA140-162 COOLER SIDE COOLER SIDE a30-4425 a30-4421 COMPRESSOR SIDE COMPRESSOR SIDE 30XA501B 30XA180-202 COOLER SIDE COOLER SIDE a30-4422 a30-4419...
  • Page 93 SINGLE PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) — Al/Cu* 30XA UNIT SIZE Total 1273 2898 1160 2089 1271 9,662 1289 2935 1175 2116 1287 9,786 1299 2959 1196 2140 1297 9,889 1315 2996 1211 1009 2167 1313 10,013 1312 3002 1219 1019...
  • Page 94 DUAL PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) — Al/Cu* 30XA UNIT SIZE Total 1273 3106 1248 2089 1271 9,959 1289 3145 1264 2115 1287 10,083 1299 3168 1285 2140 1297 10,186 1315 3206 1301 1009 2166 1313 10,310 1312 3211 1307 1019...
  • Page 95 UNITS WITHOUT PUMPS — ENGLISH MOUNTING WEIGHT (lb) — Cu/Cu* 30XA UNIT SIZE Total 2244 1970 1956 2228 8398 2286 2007 1993 2270 8555 MOUNTING WEIGHT (lb) — Cu/Cu* 30XA UNIT SIZE Total 1394 2429 1144 2368 1392 9,669 1412 2460 1159 2398...
  • Page 96 UNITS WITHOUT PUMPS — SI MOUNTING WEIGHT (kg) — Cu/Cu* 30XA UNIT SIZE Total 1018 1011 3809 1037 1030 3881 MOUNTING WEIGHT (kg) — Cu/Cu* 30XA UNIT SIZE Total 1102 1074 4386 1116 1088 4442 1127 1100 4489 1141 1114 4545 1145 1117...
  • Page 97 30XA080,082 30XA220-302 COOLER SIDE COOLER SIDE a30-4419 a30-4423 COMPRESSOR SIDE COMPRESSOR SIDE 30XA090-122 30XA325-352 COOLER SIDE COOLER SIDE a30-4424 a30-4420 COMPRESSOR SIDE COMPRESSOR SIDE 30XA400-501A 30XA140-162 COOLER SIDE COOLER SIDE a30-4421 a30-4425 COMPRESSOR SIDE COMPRESSOR SIDE 30XA180-202 30XA501B COOLER SIDE COOLER SIDE a30-4422 a30-4419...
  • Page 98 SINGLE PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) — Cu/Cu* 30XA UNIT SIZE Total 1394 3139 1280 1093 2330 1392 10,627 1410 3176 1295 1106 2357 1408 10,751 1420 3201 1317 1117 2382 1418 10,854 1436 3237 1332 1130 2409 1434 10,978 1433...
  • Page 99 DUAL PUMP UNITS — ENGLISH MOUNTING WEIGHT (lb) — Cu/Cu* 30XA UNIT SIZE Total 1394 3347 1369 1093 2330 1392 10,924 1410 3385 1385 1105 2356 1408 11,048 1420 3409 1406 1117 2382 1418 11,151 1436 3447 1422 1129 2408 1434 11,275 1433...
  • Page 100 Table 1A — Physical Data — English UNIT 30XA OPERATING WEIGHT (lb)* Al-Cu Condensers 7,674 7,831 9,959 10,083 10,186 10,310 10,326 10,563 10,471 10,681 Cu-Cu Condensers 8,398 8,555 10,924 11,048 11,151 11,275 11,291 11,528 11,436 11,646 MCHX Condensers 7,234 7,391 9,382 9,506 9,603...
  • Page 101 Table 1A — Physical Data — English (cont) UNIT 30XA OPERATING WEIGHT (lb)* Al-Cu Condensers 15,071 14,887 15,231 16,853 17,055 17,022 17,224 17,362 17,834 Cu-Cu Condensers 16,639 16,455 16,799 18,662 18,864 18,831 19,033 19,292 19,764 MCHX Condensers 14,092 13,897 14,241 15,720 15,922 15,878...
  • Page 102 Table 1B — Physical Data — SI UNIT 30XA OPERATING WEIGHT (kg)* Al-Cu Condensers 3 481 3 552 4 517 4 573 4 620 4 676 4 684 4 791 4 750 4 845 Cu-Cu Condensers 3 809 3 881 4 955 5 011 5 058...
  • Page 103 Table 1B — Physical Data — SI (cont) UNIT 30XA OPERATING WEIGHT (kg)* Al-Cu Condensers 6 836 6 753 6 909 7 644 7 736 7 721 7 813 7 876 8 089 Cu-Cu Condensers 7 547 7 464 7 620 8 465 8 556 8 542...
  • Page 104: Rigging Unit

    RIGGING UNIT (SEE FIG. 29-31) If overhead rigging is not available, the unit can be moved on roll- ers or dragged. When unit is moved on rollers, the unit skid, if The 30XA080-501 units are designed for overhead rigging and it equipped, must be removed.
  • Page 105 CAUTION - NOTICE TO RIGGERS: ALL PANELS MUST BE IN PLACE WHEN RIGGING. DO NOT ATTEMPT TO FORK THESE UNITS IF NO SKID IS SUPPLIED. NOTES: 1. 1.50 dia. (38.1mm) lifting holes provided for field supplied clevis. 2. Rig with a minimum of 25 ft (7620mm) length chains or cables. 3.
  • Page 106 13' Minimum (3962 mm) a30-5405 Fig. 30 — Unit Rigging Label Detail 30XA220-352...
  • Page 107 CAUTION - NOTICE TO RIGGERS: ALL PANELS MUST BE IN PLACE WHEN RIGGING. DO NOT ATTEMPT TO FORK THESE UNITS IF NO SKID IS SUPPLIED. NOTES: 1. 1.50 dia. (38.1mm) lifting holes provided for field supplied clevis. 2. Rig with a minimum of 25 ft (7620mm) length chains or cables. 3.
  • Page 108: Step 3 - Make Refrigerant, Cooler Fluid And

    Carrier Service technician is required. CAUTION • A Carrier Service technician must approve the work exe- cuted by the outside company. Without Carrier technician Remove the chilled water flow switch, entering and leaving supervision and approval, the equipment warranty will not water thermistors before welding connecting piping.
  • Page 109 BRAZED CAPS NOTE: Corner posts removed for clarity. Fig. 32B — 30XA501 Discharge Line Brazed Caps to be Removed A30-5639 NOTE: APPLY WET RAG TO BALL VALVES PRIOR TO BRAZING SCHRADER PORT FOR DRAWING VACUUM A30-5640 NOTE: Corner posts and coil tray removed for clarity. Fig.
  • Page 110 501A MODULE 501B MODULE A30-5638 NOTE: See Fig. 33B and 33C for detailed view of circled area. Fig. 33A — 30XA501 Liquid Line Piping Connection Location (Shown from Cooler Side) BRAZED CAPS NOTE: Corner posts removed for clarity. A30-5641 Fig. 33B — 30XA501 Liquid Line Brazed Caps to be Removed...
  • Page 111 NOTE: APPLY WET RAG TO BALL VALVES PRIOR TO BRAZING A30-5642 SCHRADER PORTS FOR DRAWING VACUUM NOTE: Corner posts removed for clarity. Fig. 33C — 30XA501 Liquid Line Piping Installed (In Field) Step C: Drawing Vacuum and Opening the Refrigerant Paths Step D: Connect Fan Wiring Use the Schrader ports shown in Fig.
  • Page 112 30XA401, 451, 476, 501 Water Line Installation Options (8 in., 11 degree elbows) per line to provide an offset so that there is enough clearance from the economizer assembly The water lines for the standard coolers for the 401, 451, 476 and for installation.
  • Page 113: General

    3. All wiring must comply with applicable local and national codes. Chilled Water Piping 4. All piping must follow standard piping techniques. Refer to Carrier System Power Wiring Design Manual or appropriate ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) handbook for details.
  • Page 114 3. All wiring must comply with applicable local and LEGEND national codes. STRAINER* 4. All piping must follow standard piping techniques. Airflow Through Condenser Refer to Carrier System Design Manual or appro- ISOLATION priate ASHRAE (American Society of Heating, Power Wiring VALVE* Refrigerating, and Air-Conditioning Engineers) Chilled Water Piping handbook for details.
  • Page 115 LEGEND 3. All wiring must comply with applicable local and national codes. 4. All piping must follow standard piping techniques. Refer to Carrier System Design Airflow Through Condenser Manual or appropriate ASHRAE (American Society of Heating, Refrigerating, and Air-Conditioning Engineers) handbook for details.
  • Page 116 a30-4413...
  • Page 117 Table 3 — 30XA Minimum and Maximum Cooler Flow Rates ITEM MINIMUM MAXIMUM Cooler Leaving Water Temperature* 40 F (4.4 C) 60 F (15 C) Cooler Entering Water Temperature† 45 F (7.2 C) 70 F (21.1 C) Nominal Flow Rate Minimum Flow Rate** Maximum Flow Rate 30XA...
  • Page 118 †For applications requiring cooler entering water temperature operation at less than 45 stitute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering water F (7.2 C), contact your local Carrier representative for unit selection using the Carrier temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft -hr-F/Btu (0.000018 m...
  • Page 119 GOOD a30-5323 a30-3185 GOOD FLOW SWITCH Fig. 41 — Tank Baffling Fig. 40 — Flow Switch T1 PP HEATER HEATER HYDRONIC PUMP PACKAGE INSIDE UNIT OUTSIDE UNIT CHILLED WATER OUT HEATER LEGEND CHILLED — Drain, -in. NPT Air Separator with Vent* D...
  • Page 120: Flooded Cooler Units

    T1 PP HEATER HEATER HYDRONIC PUMP PACKAGE INSIDE UNIT OUTSIDE UNIT CHILLED WATER OUT HEATER LEGEND — Drain, -in. NPT D — Drain, -in. NPT CHILLED Air Separator with Vent* — Expansion Tank Connection, -in. NPT WATER IN FS — Flow Switch PP —...
  • Page 121 The combination valve performs the following functions: the top. The cooler has water-side victaulic-type connections (fol- low connection directions as provided by the coupling manufac- • drip-tight shut-off valve turer). Provide proper support for the piping. If accessory security • spring closure design with a non-slam check valve grilles have been added, holes must be cut in the grilles for field •...
  • Page 122 T1 PP Chilled Water Out HEATER HEATER Chilled Water In PP T2 LEGEND — Drain, -in. NPT FS — Flow Switch PP — Pipe Plug, -in. NPT — Leaving Water Thermistor — Entering Water Thermistor — Vent, -in. NPT a30-5326 —...
  • Page 123: Dx Cooler Units

    CONTROL SLAVE CHILLER PUMP CONTROL a30-5295 MASTER CHILLER LEGEND Field-Installed Communication Bus (slashes indicate number of conductor wires) Field-Installed Wiring Optional Piping Isolation Valve Fig. 47 — Series Dual Chiller Operation (Not Recommended for DX Cooler) IMPORTANT: Automatic vents should be located in accessible locations for maintenance purposes and pro- tected from freezing.
  • Page 124 2. Install an air separator in the water loop, at the place where should be given to the points of highest temperature. It is import- the water is at higher temperatures and lower pressures — ant that the pipe be sized correctly so that free air can be moved to usually in the chilled water return piping.
  • Page 125 Heater (Optional) FS PP HYDRONIC PUMP PACKAGE INSIDE UNIT OUTSIDE UNIT Chilled Water Out Heater LEGEND — Drain, -in. NPT D — Drain, -in. NPT — Expansion Tank Connection, -in. NPT Chilled FS — Flow Switch Air Separator with Vent* PP —...
  • Page 126 DX Cooler Units with Hydronic Pump Package in. NPT fitting is installed in the inlet piping of the pump for connection to an expansion tank. Install the tank in accordance The 30XA092-162 units can be equipped with a factory-installed with the manufacturer's instructions. hydronic pump package consisting of a suction guide/strainer, pump, combination valve, internal piping and wiring connected at Figure 50 illustrates typical dual pump package.
  • Page 127: Preparation For Year-Round Operation

    a warning that power must not be turned off except when servic- ing unit. CAUTION Operation with fresh water is not fail-safe should there be a IMPORTANT: Adding antifreeze solution is the only loss of power to the chiller or to the circulating pump. Freeze certain means of protecting the unit from freeze-up if damage due to power loss or disabling chiller pump control in heater fails or electrical power is interrupted or lost...
  • Page 128 Cross break these faces. Hem these 3 edges both top and bottom. 305 [12.0] See Detail A 1880 [74.0] 180 [7.0] BAFFLE HEIGHT (X) POSITION RIGHT END LEFT END 30XA080-122 (Control box end) 1040 [41.0] 635 [25.0] 30XA142-202 200,230 Volt (Control box end) 30XA080-122 (Opposite control box end) 30XA140-202 200,230 Volt (Opposite control box end)
  • Page 129: Step 4 - Fill The Chilled Water Loop

    2. Be sure to use a cleaning agent that is compatible with all system materials. Be especially careful if the system con- Carrier’s ComfortLink controls provided have a built-in feature to tains any galvanized or aluminum components. Both deter- remind building owners or operators to clean the strainer at a pre- gent-dispersant and alkaline-dispersant cleaning agents are set time interval.
  • Page 130: System Pressurization

    090-162 FTV-5 in. If the application involves two or more chillers in a primary-sec- NOTE: Carrier recommends a differential pressure gage when ondary system, a common place for mounting the expansion measuring pressures across the pumps or balancing valves. This tank is in the chilled water return line, just before the decoupler.
  • Page 131 Head Pressure (m) ft of Fluid 3450 RPM 6.19 in (45.7) 150 5.75 in (36.6) 120 5.50 in 5.25 in 5.00 in (27.4) 90 4.75 in 4.50 in 20 hp (18.3) 60 15 hp 10 hp 7.5 hp (9.1) 30 5 hp 3 hp NPSHr...
  • Page 132: Pump Modification/Trimming

    –20°F (–29°C), except in the case of a power failure. The Carrier warranty does not cover damage Once the combination valve is set, note the stem position. If later due to freezing.
  • Page 133: Step 5 - Make Electrical Connections

    Wiring supply. If the unit is equipped with this option, all field connections for CCN (Carrier Comfort Network) should be made power wiring should be made to the non-fused disconnect at TB (terminal block) 3. Consult the CCN Contractor’s Manual since no terminal blocks are supplied.
  • Page 134 LEGEND — Alarm — Energy Management HSCCR — High Short Circuit Current Rating — Minimum Load Valve — National Electric Code — Chilled Water Pump PMPI — Chilled Water Pump Interlock PVFD — Chilled Water Pump VFD SCCR — Short Circuit Current Rating —...
  • Page 135 Fig. 58 — Control and Power Wiring Schematic (cont)
  • Page 136 Notes for Control and Power Wiring Schematic 1. Factory wiring is in accordance with UL 1995 standards. Field chilled water pump 2 (PMP 2) starter. The maximum load allowed modifications or additions must be in compliance with all applica- for the chilled water pump relay is 5 VA sealed, 10 VA inrush at ble codes.
  • Page 137 A30-5603 A30-5478...
  • Page 138 A30-5479...
  • Page 140 Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MCA MOCP Fuse MCA MOCP Fuse...
  • Page 141 Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MCA MOCP Fuse MCA MOCP Fuse...
  • Page 142 Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) FANS Size...
  • Page 143 Table 5 — 30XA080-500 Electrical Data, Single Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) FANS Size...
  • Page 144 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS Size Size...
  • Page 145 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS Size...
  • Page 146 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 7.5 HP PUMP, 3450 RPM 10 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS...
  • Page 147 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 7.5 HP PUMP, 3450 RPM 10 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS...
  • Page 148 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse 1 PH, (3 Ph) FANS Size 60 Hz MOCP 230-60 —...
  • Page 149 Table 6 — 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont) UNIT VOLTAGE 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse 1 PH, (3 Ph) FANS Size 60 Hz MOCP 460-60 8/14 —...
  • Page 150 Table 7 — 30XA140-501 Electrical Data, Single Point (High Ambient Option) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM 7.5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MCA MOCP Fuse MCA MOCP Fuse 1 PH,...
  • Page 151 Table 7 — 30XA140-501 Electrical Data, Single Point (High Ambient Option) (cont) UNIT VOLTAGE 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) FANS Size Size...
  • Page 152 Table 8 — 30XA140-501 Electrical Data, Dual Point (High Ambient Option) UNIT VOLTAGE NO HYDRONIC PACKAGE 5 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS Size Size...
  • Page 153 Table 8 — 30XA140-501 Electrical Data, Dual Point (High Ambient Option) (cont) UNIT VOLTAGE 7.5 HP PUMP, 3450 RPM 10 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse MOCP Fuse 1 PH, (3 Ph) Min Max FANS Size...
  • Page 154 Table 8 — 30XA140-501 Electrical Data, Dual Point (High Ambient Option) (cont) UNIT VOLTAGE 15 HP PUMP, 3450 RPM CONTROL CIRCUIT NUMBER UNIT Supplied Voltage V-Hz 30XA COND MOCP Fuse 1 PH, (3 Ph) FANS Size 60 Hz MOCP 230-60 383.8/256.9 600/350 660.8/436.2...
  • Page 155 Table 9 — Compressor and Fan Electrical Data COMPRESSOR CONDENSER FANS UNIT LRA (All Units) LRA (All Units) LRA (All Units) 30XA VOLTAGE NUMBER High High High UNIT V-Hz OF COND High Ambient Standard Ambient Standard Ambient Standard SIZE (3 Ph, FANS* Ambient Standard...
  • Page 156 Table 9 — Compressor and Fan Electrical Data (cont) COMPRESSOR CONDENSER FANS UNIT LRA (All Units) LRA (All Units) LRA (All Units) 30XA VOLTAGE NUMBER High High High UNIT V-Hz OF COND High Ambient Standard Ambient Standard Ambient Standard SIZE (3 Ph, FANS* Ambient...
  • Page 157: Non-Ccn Communication Wiring

    NON-CCN COMMUNICATION WIRING For dual chiller control a CCN bus must be connected between the two modules (Fig. 59). See the Carrier Comfort Network Commu- The 30XA units offer several non-CCN translators. Refer to the nication Bus Wiring section for additional information.
  • Page 158: Step 6 - Install Accessories

    MINIMUM LOAD ACCESSORY mA. The switch is located behind the display. The cover must be Contact your local Carrier representative for more details if a min- removed and the display will snap off to access this switch. imum load accessory is required for a specific application. For in- The set point is defined by Parameter 20-21, Setpoint 1.
  • Page 159: Service Options

    The remote service port is housed in a weather-proof enclosure with a communication port to plug in the Navigator™ device. CAUTION Contact your local Carrier representative for more details. For in- stallation details, refer to separate installation instructions supplied When charging, circulate water through the cooler at all times with each accessory package.
  • Page 160 To wire the UPC Open controller to the BAS network: To install a BT485 terminator, push the BT485 on to the BT485 connector located near the BACnet connector. 1. Pull the screw terminal connector from the controller's BAS Port. NOTE: The BT485 terminator has no polarity associated with it. 2.
  • Page 161 BT485 TERMINATOR BACNET CONNECTION POWER LED (BAS PORT) Tx1 LED Rx1 LED Tx2 LED Rx2 LED BACNET BAUD RATE DIP SWITCHES EIA-485 JUMPERS ADDRESS ROTARY SWITCHES RUN LED ERROR LED Fig. 61 — UPC Open Controller Fig. 62 — Network Wiring...
  • Page 162: Wiring

    — Communications Plenum Rated — Fluorinated Ethylene Polymer — Tinned Copper © 2013 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300110-01 Printed in U.S.A.

Table of Contents