Remote cooler accessory 60 hz

Advertisement

Quick Links

Part Numbers 00EFN900003000A, 00EFN900003100A
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Cooler and Economizer Removal. . . . . . . . . . . . . . . . . 4
Remote Cooler and Economizer Installation. . . . . 10
SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning
equipment can be hazardous due to system pressures, electrical
components, and equipment location. Only trained, qualified
installers and service technicians should install, start-up, and
service this equipment.
When working on air-conditioning equipment, observe
precautions in the literature and on tags, stickers, and labels
attached to the equipment. Follow all safety codes. Wear safety
glasses and work gloves. Use care in handling equipment.
Be sure power to equipment is shut off before performing
maintenance or service. Lock out and safety-tag all
disconnects.
GENERAL
The remote cooler accessory allows for the indoor reloca-
tion of the cooler on 30XA080-350 units as another means of
freeze protection. When the cooler is located in a heated space,
an anti-freeze solution is not needed and the performance
degradation associated with antifreeze solution can be avoided.
Maximum separation of the 30XA base unit and cooler is
limited to 50 lineal ft (15.25 m) or 75 equivalent ft (22 m) of
piping. For more information, refer to the Carrier Piping De-
sign manual.
The liquid and economizer lines between the exterior-
installed unit and the remote, interior-installed cooler must
have pressure relief devices installed in accordance with
ASHRAE 15 (American Society of Heating, Refrigeration, and
Air Conditioning Engineers) and local codes.
Units to be modified for a remote cooler application must
have the following options:
• Factory-installed suction service valve option.
• Condenser coil type:
— Aluminum fin and copper tube
— Pre-coat aluminum fin and copper tube
— E-coat aluminum fin and copper tube
— Copper fin and copper tube
— E-coat copper fin and copper tube
NOTE: The microchannel heat exchanger option can NOT use
the remote cooler accessory.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300012-01
Book 2
Tab
5c

Installation Instructions

Printed in U.S.A.
Remote Cooler Accessory
The application is limited to the following constraints:
• Operating chilled water temperature is between 40 and 55 F
(4.4 and 12.8 C). When the remote cooler is applied, the
cooler heaters will not function, so it is critical to maintain the
water temperature above the freezing point at all times. If the
water temperature falls below the freezing point, the cooler
does not have protection to keep the water from freezing.
• The interior space temperature where the cooler will be
installed must be maintained at a minimum of 50 F (10 C).
• Underground refrigerant piping is NOT permitted for this
application.
See Table 1 for accessory package usage and see Table 2 for
accessory package contents. In addition to the parts supplied
with each accessory package, the following material must be
field-supplied:
• Refrigerant grade liquid and suction line copper piping for
30XA080-120: circuits A and B and 30XA140-160: circuit
B (length determined by installation). See Tables 3A and 3B
for pipe sizes.
• Schedule 40 steel pipe for 30XA140-160: circuit A and
30XA180-350: circuits A and B (length determined by
installation). See Tables 3A and 3B for pipe sizes.
• 350 psig pressure relief valves and fittings (2 per circuit)
• Suction line tubing insulation (length determined by
installation)
• Economizer line tubing insulation (length determined by
installation)
1
/
in. strain relief (2)
2
• Conduit (length determined by installation)
• ASME (American Society of Mechanical Engineers) B16.9
stub end (4 in. [102 mm]), Schedule 40 Steel (one needed
for 30XA140-160, two needed for 30XA180-350)
• ASME B16.5 Class 600 pipe flange (4 in. [102 mm]) with
field-modified extra mounting hole (one needed for
30XA260-300, two needed for 325, 350)
• Flange mounting hardware
• Extra flange gaskets (if necessary)
The 30XA units use R-134a refrigerant. No other refriger-
ant may be used in this system. Suction tubing design pres-
sure is 220 psig (1517 kPa). Economizer and liquid tubing
design pressure is 350 psig (2413 kPa). Failure to use gage
set, hoses, and recovery systems designed to handle
R-134a refrigerant may result in personal injury and equip-
ment damage. If unsure about equipment, consult the
equipment manufacturer.
Table 1 — Accessory Package Usage
30XA UNIT SIZE
080-200
220-350
Form 30XA-7SI
Pg 1
30XA080-350
60 Hz
PACKAGE REQUIRED
00EFN900003000A
00EFN900003100A
1-07
Replaces: New

Advertisement

loading

Summary of Contents for Carrier 00EFN900003000A

  • Page 1: Installation Instructions

    Maximum separation of the 30XA base unit and cooler is limited to 50 lineal ft (15.25 m) or 75 equivalent ft (22 m) of piping. For more information, refer to the Carrier Piping De- sign manual. The liquid and economizer lines between the exterior-...
  • Page 2 ACCESSORY PACKAGE ITEM NO. PART NO. 00EFN900003000A 00EFN900003100A Choose a space that can support the weight of the cooler and economizer with service clearances and area for refrigerant piping. Field-supplied piping must be limited to less than 50 lineal ft (15.25 m) or 75 equivalent ft (22 m) in length.
  • Page 3: Indoor Location

    LEGEND ... Liquid Line Economizer Line Suction Line a30-4509 Fig. 1 — 30XA Unit and Cooler Level, Piping Parallel (Single Circuit Shown) LEGEND ... Liquid Line Economizer Line Suction Line a30-4510 Fig. 2 — 30XA Unit and Cooler Level, Piping Elevated (Single Circuit Shown) LEGEND ...
  • Page 4: Installation

    1. Inspect package contents for missing or damaged parts. File a claim with the shipping agency if parts are damaged and notify your local Carrier representative if any item is missing. 2. Determine the new location for the cooler. Ensure that the...
  • Page 5 Table 4A — Refrigeration Line Sizes (English) DOUBLE SUCTION RISERS SUCTION LINE 30XA Circuit A UNIT Circuit A Circuit B Riser A Riser B SIZE (in.) (in.) (in.) DOUBLE SUCTION RISERS SUCTION LINE 30XA Circuit A UNIT Circuit A Circuit B Riser A SIZE (mm)
  • Page 6 13/16 (20) 8-9/32 (13) (210) DETAIL SCALE 2:1 TYP 6 PLACES SEE DETAIL 14-11/32 (364) NOTES: 1. Measurements are shown in inches (millimeters). 2. Recommended service clearance around the cooler is 36 in. (914 mm). 3. Recommended cooler tube removal area (either end) is 109 in. (2769 mm). 13/16 (20) 10-23/32...
  • Page 7 13/16 (20) 11-3/16 (284) (13) DETAIL SCALE 2:1 TYP 6 PLACES SEE DETAIL 18-3/8 (466) NOTES: 1. Measurements are shown in inches (millimeters). 2. Recommended service clearance around the cooler is 36 in. (914 mm). 3. Recommended cooler tube removal area (either end) for 30XA180, 200 is 109 4.
  • Page 8 22-7/8 (581) 30-3/8 (770) SIDE VIEW 29-3/8 (746) 2 x Ø 7/16 (11) TOP VIEW NOTES: 1. Measurements are shown in inches (millimeters). 2. Recommended service clearance around the economizer is 36 in. (914 mm). Fig. 5A — 30XA090-160 Economizer Dimensions 23-1/32 (585) 30-3/4...
  • Page 9 a30-4518 30 4518...
  • Page 10 See Fig. 9. NOTE: The original flanges on the cooler and cut from the 30XA base unit may still be usable. However, Carrier recom- mends and has provided in the accessory kit, parts necessary to replace both the cooler pipe flange and the suction flange.
  • Page 11 12. Using the accessory-supplied M6 screws (3000A or 3100A: Item 6), install the accessory-supplied junction box (3000A or 3100A: Item 5) at the desired location where the entering and leaving water thermistor cables can be conveniently spliced. One or two knockouts can be used.
  • Page 12 Compressor Flange Gasket (3100A: Item 9), Loose Pipe Flange (3100A: Item 11) LEGEND 3000A — Accessory Package Part No. 00EFN900003000A (30XA080-200) 3100A — Accessory Package Part No. 00EFN900003100A (30XA220-350) Item — Item No. (See Table 2) *Copper connection. Circuit B...
  • Page 13 Compressor Flange Gasket (3100A: Item 9), Loose Pipe Flange (3100A: Item 11) LEGEND 3000A — Accessory Package Part No. 00EFN900003000A (30XA080-200) 3100A — Accessory Package Part No. 00EFN900003100A (30XA220-350) Item — Item No. (See Table 2) *Copper connection. Table 7 — Additional Refrigerant Charges Required...
  • Page 14 PRESSURE RELIEF VALVES (FIELD- SUPPLIED) 30XA ECONOMIZER LINE MANUAL SHUTOFF VALVE LIQUID LINE (30XA TO ECONOMIZER) FLANGE CONNECTION SUCTION LINE NOTE: All shaded piping is field supplied and installed. Fig. 7 — Line Piping and Connections (1 Circuit Shown) RED . FROM COOLER 90 DEGREE...
  • Page 15 Fig. 10 — Unbolt Portion Between Flex Connector and Cooler (30XA140, 160: Circuit A and 30XA180-350: All Circuits) ASME B16.9 STEEL STUB END (FIELD-SUPPLIED) PIPE FLANGE (ACCESSORY-SUPPLIED, MOUNTING SEE TABLE 6) BRACKET Fig. 11 — Connect Steel Suction Line at the 30XA Base Unit (Shown) and Cooler (30XA140, 160: Circuit A and 30XA180-350: All Circuits)
  • Page 16 OAT — Outdoor Air Temperature SPT — Suction Pressure Transducer Fig. 13 — Thermistor Connections Copyright 2007 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300012-01 Book 2 Fig.