Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 81

Air-cooled liquid chillers
Table of Contents

Advertisement

Possible Causes -- If this condition
is encountered,
check the
following items:
Compressor
operating beyond the operation envelope.
Incorrect MTA setting.
Compressor
Locked
Rotor
Almm 111-05 -- Circuit A (A1.05)
Almm 112-05 --Circuit
B (B 1.05)
Almm 113-05 -- Circuit C (C1.05)
Criteria .fbr Trip --
The _flmm criterion
is checked
during
stall-up when the compressor
is ON. This tdarm will be gener-
ated if the CPM board detects a high motor current compared
with the MTA (must trip alnps) setting for more than 450 ms.
Action to be _iken -- The compressor
will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition
is encountered,
check the
following items:
compressor
mechanical
f:filure
unloader
slide valve failure
compressor
motor failure
Compressor
Phase Loss
Almm 111-06 -- Circuit A
Almm 112-06-
Circuit B
Almm 113-06 -- Circuit C
Almm 111-07 -- Circuit A
Almm 112-07 -- Circuit B
Almm 113-07-
Circuit C
Almm 111-08 -- Circuit A
Almm 112-08-
Circuit B
Almm 113-08-
Circuit C
LI (AI.06)
LI (BI.06)
LI (C1.06)
L2 (A 1.07)
L2 (B1.07)
L2 (C1.07)
L3 (A 1.08)
L3 (BI.08)
L3 (C1.08)
CriWria .fbr Trip --
The alarm criteria
are checked
during
startup when the compressor
is ON. This _darm will be gener-
ated if:
The current unbalance
on any of the 3 phases is greater than
65% for more than 1 second continuously
during start-up.
The current
unbalance
on any of the 3 phases
is greater
than 65% for more
than 200 ms continuously
during
runtime.
Action to be _iken -- The compressor
will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition
is encountered,
check the
following items:
power failure
blown fuse or tripped circuit breaker
power wiring errol_ or loose termin_fls
Compressor
Low Current
Almm 111-09 -- Circuit A (A1.09)
Almm 112-09-
Circuit B (B 1.09)
Almm 113-09 -- Circuit C (C1.09)
Cl4wria ._br Trip --
The alarm criteria me checked
when the
compressor
is ON. This alarm will be generated
if:
The current
is less than 15% MTA on all three legs for
more than 450 ms for Wye-Delta
start units.
If the current
is less than 15% of MTA on all three legs
for more than 1 second
for direct start units.
Action to be _ken
-- The compressor
will be stopped.
Reset Method -- Manual
Possible Causes -- If this condition
is encountered,
check the
following items:
power failure
blown fuse or tripped circuit breaker
deenergized contactor
faulty current toroid
Compressor
Wve-Delta
Starter Current
Increase
Failure
Almm 111-10 -- Circuit A (AI. 10)
Almm 112-10 -- Circuit B (B 1.10)
Almm 113-10 -- Circuit C (CI.10)
Criteria ._br Trip --
The almm criterion
is checked
during
compressor
start-up. This almm will be generated
if the current
in Delta mode is not more than 25% greater than the cunent
in
Y mode within 550 ms.
Action to be _ken
-- The compressor
will be stopped.
Reset Method--
Manual
Pos,ffble Causes -- If this condition is encountered,
check the
following items:
power supply failure to the delta contactor
faulty wiring to the delta contactor
faulty CPM board
faulty current toroid
Compressor
Contactor
Failure
Alarm 111- 11 -- Circuit A (A 1.11 )
Alarm 112-11 -- Circuit B (B 1.11 )
Alarm 113-11 -- Circuit C (C 1.11 )
CriWria ._br Trip --
The almm criterion
is checked
during
compressor
shut-down. This alarm will be generated
if the cur-
rent is greater than 15% of the MTA on at least one phase for
10 continuous
seconds.
Action to be _ken
-- The compressor
will be stopped.
Reset Method--
Manual
Possible Causes -- If this condition is encountered,
check the
following items:
faulty or welded contactor
faulty wiring
faulty CPM board
Compressor
Unable to Stop Motor
Alarm 111-12 -- Circuit A (A 1.12)
Alarm 112-12--
Circuit B (131.12)
Alarm 113-12 -- Circuit C (C 1.12)
Criwria ._br Trip --
The almm criterion
is checked
during
compressor
shut-down.
This alarm will be generated
if aller
three attempts to turn off the compressor
outputs and the cur-
rent is still greater than 15% of the MTA on at least one phase
for 10 continuous
seconds.
Action to be _ken
-- The compressor
will be stopped.
Reset Method--
Manual
Possible Causes -- If this condition is encountered,
check the
following items:
faulty or welded contactor
faulty wiring
Compressor
Phase Reversal
Alarm 111-13 -- Circuit A (A 1.13)
Alarm 112-13-
Circuit B (BI.13)
Alarm 113-13 -- Circuit C (C 1.13)
CriWria ,fbr Trip --
The almm criterion
is checked
during
compressor
st_ut-up. This alarm will be generated
if the CPM
board detects a phase reversed from the cunent
toroid.
Action to be _ken
-- The compressor
will be stopped.
Reset Method--
Manual
Possible Causes -- If this condition is encountered,
check the
following items:
if power supply lead at the terminal block is not operating at
the correct phase
if power supply is crossed when going through the current
toroid
Compressor
MTA Configuration
Fault
Alarm 111-14 -- Circuit A (A 1.14)
Alarm 112-14 -- Circuit B (131.14)
Alarm 113-14 -- Circuit C (C 1.14)
C;4teria_sr
Trip -- The _dmm criterion is checked whether the
compressor
is ON or OFF. This alarm will be generated
if the
MTA setting is out of the allowed MTA range.
81