Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 53

Air-cooled liquid chillers
Table of Contents

Advertisement

2.
[nsert and secure the led (+) wire to terminal 5 of the
space temperature
sensor terminal block.
3. [nsert and secure the white (ground) wire to terminal 4 of
the space temperature
sensol:
4. Insert and secure the black (-) wire to terminal 2 of the
space temperatme
sensor
IMPORTANT:
The
cable
selected
for
the RJll
connector
wiring
MUST
be identical
to the CCN
communication
bus wire used for the entire network.
Refer to Table 11 for acceptable
wiring.
5. Connect the other end of the communication
bus cable to
the remainder
of the CCN communication
bus.
NOTE: The Energy Management
Module (EMM)
is required
for this accessoly.
TRANSDUCERS
-- There are four pressure transducers
per
circuit, and two different
types of transducers:
low pressure
(green connector)
and high pressure (black connector).
Ix>w Pressure Type: Suction Pressme Transducer
(SPT), Econ-
omizer Pressure Transducer
(EPT).
High Pressure
Type: Dischmge
Pressure
Transducer
(DPT),
Oil Pressure
Transducer
(OPT).
See Fig. 29 for transducer
locations.
Table 29 -- Thermistor Identification
THERMISTOR
ID
DESCRIPTION
RESISTANCE
AT 77 F (25 C)
CONNECTION
POINT
EWT
Entering Water Thermistor
5k £!
MBB-J6-CH2
LWT
Leaving Water Thermistor
5k £2
MBB-J6-CH1
OAT
Outdoor Air Thermistor
5k £2
MBB-J6-CH4
SGTA*
Circuit A Suction Gas Thermistor
5k £2
EXVA-J3-THA
SGTB*
Circuit B Suction Gas Thermistor
5k £2
EXVB-J3-THA
SGTC
Circuit C Suction Gas Thermistor
5k £!
EXVC-J3-THA
DGTA
Circuit A Discharge Gas Thermistor
5k £2
CPM-A-J9-CH02
DGTB
Circuit B Discharge Gas Thermistor
5k £!
CPM-B-J9-CH02
DGTC
Circuit C Discharge Gas Thermistor
5k £2
CPM-C-J9-CH02
ECTA
Circuit A Economizer Thermistor
5k £!
EXVA-J3-THB
ECTB
Circuit B Economizer Thermistor
5k £2
EXVB-J3-THB
ECTB
Circuit C Economizer Thermistor
5k £2
EXVC-J3-THB
DUAL
Dual Chiller LWT Thermistor
5k £2
MBB-J6-CH3
CAMT
Circuit A Motor Temperature
5k £2
CPM-A-J9-CH01
CBMT
Circuit B Motor Temperature
5k £2
CPM-B-J9-CH01
CCMT
Circuit C Motor Temperature
5k £2
CPM-C-J9-CH01
SPT
Space Temperature Thermistor
1Ok £!
EMM-J6-CH2
*SGTA and SGTB for 30XA080 units are connected to the EXVA board.
O-R_ASSNUT
3'8 B24FO S ELL
Fig. 26 -- 5K Thermistor (Sensor 00PG000008105A,
Connector: HY06AM016)
j_,/1/4-18
NPT
6" MINIMUM
_CL¢222_R_4._1.188
,n._
2.315 in._
I
REMOVAL
Fig. 27 -- Dual Leaving Water Thermistor Well (00PPG00000800A)
I
SENSOR
I
i-
I
I
I
--v-
!
I
I
I
.....
i
7
i
I
I
Fig. 28 -- Typical Remote Space Temperature Sensor (33ZCT55SPT)