Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 74

Air-cooled liquid chillers
Table of Contents

Advertisement

Suction
Pressure
Transducer
Failure
Alarln 27 -- Cimuit A (Pl:04)
Alarm 28 -- Circuit B (171.05)
Alarm 29 -- Circuit C (1'1.06)
Criteria fsr Trip -- The criteria are tested whether the circuit is
ON or OFE The akum is generated
if one of the following
criteria is met:
1. If the voltage as sensed by the MBB or Fan Board C is
0 vdc, which corresponds
to the Navigato( r_'l display of
-7 psi (-48.3 kPa).
2. The circuit
is ON in cooling
mode and the Saturated
Suction
Temperature
(SST)
for the circuit
is greater
than the Entering
Water
Temperature
for more
than
60 seconds.
Action to be Taken -- The circuit is shut down immediately, or
not allowed to start.
Reset Method
1. Automatic,
once the transducer
voltage
is greater than
0 vdc, which corresponds
to the Navigator
display of a
value greater than -7 psi (-48.3 kPa).
2. Automatic
once the circuit's
saturated
suction tempera-
ture is lower than the Leaving Water Temperature
by 3 ° F
(1.6 ° C). If this criterion trips the alarm 3 times within a
24-hour period, the alarm changes to a manual reset.
Pos_ffble Causes -- If this condition
is encountered,
check the
following
items:
sensor wiring to Main Base Board
(Alarms
27 and 28)
sensor wiring to Fan Board C (Alarm 29)
board for a faulty channel
faulty transducer
faulty leaving water temperature
sensor
unit configuration
Reclaim Pumpdown
Pressure
Transducer
Alarm 30 -- Circuit A (Pr07)
Alarm 31 -- Circuit B (Pl:08)
NOTE:
Alarms
30 and 31 me not used or supported.
If this
condition is encountered,
confirm machine configuration.
Oil Pressure
Transducer
Alarm 32 -- Circuit A (Pl: 10)
Alarm 33 -- Circuit B (Pl: 11)
Alarm 34 -- Circuit C (Pl: 12)
Criteiqafi_r Trip -- The criteria are tested whether the circuit is
ON or OFE The alarm is generated
if one of the following
cri-
teria is met:
1. If the voltage as sensed by the MBB or Fan Board C is
0 vdc, which
corresponds
to the Navigator
display
of
-7 psi (-48.3 kPa).
2. The circuit is OFF and outside air temperature
is below
35.6 F (2 C).
3. The circuit is OFF and the fluid type is brine.
Action to be Taken -- The circuit is shut down immediately,
or
not allowed to start.
Reset Method
--
Automatic,
once the transducer
voltage
is
greater than 0 vdc.
Possible Causes -- If this condition
is encountered,
check the
following
items:
sensor wiring to CPM board
board for a faulty channel
faulty transducer
plugged oil filter
faulty oil solenoid
valve coil
stuckoil
solenoid
valve
confirm
unit configuration
Economizer
Pressure
Transducer
Failure
Altuln 35 -- Circuit A (Pl: 13)
Altmn 36 -- Circuit B (1'1. 14)
Akum 37 -- Circuit C (Pl: 15)
Cl4wriafi_r Trip -- The criteria are tested whether the circuit is
ON or OFF. The alarln is generated
if the voltage as sensed by
the MBB or Fan Board C is 0 vdc, which corresponds
to the
Navigator display of-7
psi (-48.3 kPa).
Action to be Taken -- The circuit is shut down immediately,
or
not allowed to start.
Reset Method
--
Automatic,
once the transducer
voltage
is
greater than 0 vdc, which conesponds
to the Navigator display
of a value greater than -7 psi (-48.3 kPa).
Possible Causes -- If this condition
is encountered,
check the
following items:
sensor wiring to EXV Board
EXV board for a faulty channel
faulty transducer
faulty economizer
EXV or EXV wiring
faulty economizer
EXV channel on the board
closed or partially closed
suction service valve
confirm
unit configuration
Loss of Communication
with Compressor
Board
Al_u'ln 38 -- Complessor
Board A (Co.AI)
Al+uln 39 -- Compressor
Board B (Co.B 1)
Al+um 40 -- Compressor
Board C (Co.C 1)
CriWria fi+r Trip -- The +flarm criterion is tested whether the
unit is ON or OFF. If communication
with the Compressor
Protection Module Board (CPM) is lost for a period of 10 sec-
onds, the alarm will be generated.
A++ion to be Taken --
The affected compressor
will be shut
down.
Reset Method
-- Automatic,
if communication
is established.
If called for. the compressor
will stmt normally.
Possible Causes -- If this condition
is encountered,
check the
following items:
power supply
to the affected
CPM board
address of the CPM
local equipment
network
(LEN) wiring
confirm
unit configuration
Loss of Communication
with EXV Board
Aku'm 41 -- Circuit A, EXV Board A (Co.A 1)
Altum 42 -- Circuit B, EXV Board B (Co.B2)
Akum 43 -- Circuit C, EXV Board C (Co.C3)
CriWria fi_r Trip -- The alarm criterion is tested whether the
unit is ON or OFF. If communication
with EXVA, B or C is
lost for a period of 10 seconds, the alarm will be triggered.
A_Tion to be Taken -- [f running, Circuit A, B or C will shut
down normally. If Circuit A, B or C is not operating,
it will not
be allowed to start.
Reset Method
-- Automatic,
if communication
is established,
the unit will start normally.
Possible Causes -- If this condition
is encountered,
check the
following items:
power supply to EXVA, B or C
address of the EXV board
local equipment
network
(LEN) wiring
confirm
unit configuration
Alarm 44 -- Loss of Communication
with Fan Board
1
CriWria._sr
Trip -- The criterion
is tested whether the unit is
ON or OFF. If communication
with Fan Board A is lost for a
period of 10 seconds, the alarm will be triggered.
74