Carrier 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions page 69

Air-cooled liquid chillers
Table of Contents

Advertisement

Table 39 -- Alarm Codes (cont)
PREFIX
SUFFIX
ALARM
ACTION
TAKEN
RESET
CODE
CODE
NUMBER
ALARM
DESCRIPTION
BY CONTROL
TYPE
PROBABLE
CAUSE
Pr
15
37
Circuit
C Economizer
Circuit shut down or
Automatic
Pressure
Transducer
not allowed
to start
Co
A1
38
B1
39
C1
40
E1
41
E2
42
E3
43
F1
44
Loss of communication with
Compressor Board A
Loss of communication with
Compressor Board B
Loss of communication with
Compressor Board C
Loss of communication with
EXV Board A
Loss of communication with
EXV Board B
Loss of communication with
EXV Board C
Loss of communication with
Fan Board 1
REASON FOR ALARM
Measured voltage is
0 dc
No communication
with CPM board
No communication with
EXV board
Affected
compressor shut
down
Affected
compressor
shut down
Automatic
Automatic
Faulty transducer,
wiring error, failed CPM
board
Wrong CPM address,
wrong unit configura-
tion, wiring error, power
loss, failed
CPM board
Wrong EXV board
address, wrong unit
configuration, wiring
error, power loss,
failed EXV board
No communication
with
Circuit
A/B shut
Automatic
Wrong
board address,
fan board
down or not allowed
wrong
unit configura-
to start (080-120
tion, wiring
error, loss
ton), Circuit
A shut
of power, failed board
down or not allowed
to start
(130-500
ton)
F2
45
Loss of communication
with
No communication
with
Circuit B shut down
Automatic
Wrong
board address,
Fan Board 2
fan board
or not allowed
to
wrong
unit configura-
start (130-500
ton)
tion, wiring
error, loss
of power, failed board
F3
46
Loss of communication
with
No communication
with
Circuit C shut down
Automatic
Wrong
board address,
Fan Board 3
fan board
or not allowed
to
wrong
unit configura-
start (400-500
ton)
tion, wiring
error, loss
of power, failed board
No communication
with
None
Automatic
Configuration
error
free cooling
board
No communication with
EMM board
01
O2
O3
Loss of communication
with
Free Cooling
Board
1
Loss of communication
with
Free Cooling
Board 2
Loss of communication
with
Energy Management
NRCP2*
Board
Disable or not allow
EMM functions
3 step and 4-20 mA
and space tempera-
ture reset, occu-
pancy override
and
ice build)
None
Loss of communication
with
Heat Reclaim
Board
Loss of communication
with
AUX Board 6
Cooler
Freeze
Protection
47
48
49
Automatic
Automatic
O4
5O
05
51
01
52
No communication
with Free Cooling
Board
Wrong
module
address,
wrong
unit
configuration,
wiring
error, power loss to
module,
failed module
Configuration error
P
Entering
or leaving ther-
Unit shut down or
Automatic,
first
Faulty thermistor,
faulty
mistor sensed
a tempera-
not allowed
to start
occurrence
in
wiring,
low water flow,
ture at or below freeze
24 hours;
low loop volume, fouled
point
manual
if
cooler,
or freeze
multiple
alarms
conditions
within 24 hours
--
None
Automatic
Configuration
error
Low saturated
suction
temperatures
detected
for
a period of time
EXV>98%,
suction
superheat
> 30 F,
and SST<MOP
for more
than 5 minutes
02
53
03
54
04
55
05
56
06
57
07
58
08
59
09
60
10
61
Condenser
Freeze
Protection
Circuit
A
Condenser
Freeze
Protection
Circuit
B
Condenser
Freeze
Protection
Circuit
C
Circuit
A Low Suction
Temperature
Circuit
B Low Suction
Temperature
Circuit
C Low Suction
Temperature
Circuit
A High Suction
Superheat
Circuit
B High Suction
Superheat
Circuit
C High Suction
Superheat
LEGEND
Automatic,
first
occurrence
in
24 hours;
manual
if
multiple
alarms
within 24 hours
Manual
CON
--
Carrier
Comfort
Network®
CPM
--
Compressor
Protection
Module
EMM
--
Energy
Management
Module
EXV
--
Electronic
Expansion
Valve
MOP
--
Maximum
Operating
Pressure
MTA
--
Must Trip Amps
OAT
--
Outdoor
Air Temperature
SST
--
Saturated
Suction
Temperature
UL
--
Underwriters'
Laboratories
*NRCP2
is the Energy
Management
Board.
Circuit shut down
Circuit
shut down
Faulty thermistor,
faulty
wiring,
low water flow,
low loop volume, fouled
cooler,
or freeze
conditions
Faulty transducer,
faulty wiring,
faulty
thermistor,
faulty EXV,
low refrigerant
charge,
plugged
or restricted
liquid line
69