can be viewed on the PIC6 OUTPUTS screen. Oil sump tempera-
ture can be viewed on the PIC6 Main screen.

Software Configuration

WARNING
Do not operate the chiller before the control configurations
have been checked and a Control Test has been satisfacto-
rily completed. Protection by safety controls cannot be
assumed until all control configurations have been con-
firmed. Do not assume the values in the chiller are correct.
They should match the chiller labels and data sheets for the
selection. If you have questions contact the Carrier Techni-
cal Service Manager or Service Engineering.
Consult the 23XRV with PIC6 Controls Operation and Trouble-
shooting manual for controls-related issues. As the unit is config-
ured, the configurations should be written down or a file should be
generated using ProView service tool to have settings for any fu-
ture needs. When installing new software, be sure to select to keep
all configuration data so that all data does not have to be reentered
manually. If new parameters are added to the new software they
will need to be manually configured. As the 23XRV unit is config-
ured, all configuration settings should be written down. A log,
such as the one shown on pages CL-1 to CL-10, provides a conve-
nient list for configuration values.
It is recommended that all control configuration tables be upload-
ed via Service Tool and stored for reference when the software
configuration is complete.

Input the Design Set Points

To access the set point screen, press the Main Menu icon on the
Home screen. Figure 33 is an example of the 23XRV TP home
screen and Fig. 34 is an example of the 23XRV TT/TQ home
screen.
Fig. 33 — 23XRV TP Home Screen
Fig. 34 — 23XRV TR/TQ Home Screen
Then, at Main Menu (Fig. 35), select Set Points in order to display
the menu (Fig. 36).
Fig. 35 — Main Menu
Fig. 36 — Set Points Menu
The setpoint can be set for either Entering Chilled Water (ECW)
or the default Leaving Chilled Water (LCW). ECW control option
can be enabled by setting EWT Control Option = Enable.
Additionally set Base Demand Limit if different from 100%.

Input the Local Occupancy Schedule

Access the Occupancy icon located in the Main Menu. Here the
Occupancy Schedule and Holiday Schedule for the chiller can be
configured. The default Occupancy Schedule is for both Local
Schedule (OCCPC01S), shown in Fig. 37, and Network Schedule
(OCCPC03S) to be set for 24 hours occupied, 7 days per week in-
cluding Holidays.
Fig. 37 — Occupancy Schedule (LOCALOCC), Local
36
Schedule