15 Troubleshooting
l System Error
Event name
System Error
Meaning
A hardware error was detected during self-diagnosis of the hardware.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
Hardware has failed.
A memory error occurred due to
a transient cause, such as a soft-
ware error or excessive noise.
Attached in-
Attached information 1: System information, status code
formation
Attached information 2: System information, status code
Attached information 3: System information, status code
Attached information 4: System information, status code
Precautions/
None
Remarks
15-216
Source details NX Unit
Minor fault
Recovery
Continues.
Operation
Data type
None
Correction
Cycle the power supply. If the er-
ror occurs again, replace the
Unit.
NX-series Safety Control Unit/Communication Control Unit User's Manual (Z395)
Event code
05200000 hex
Detection tim-
ing
Cycle the pow-
Log category
er supply to the
Unit.
The Unit stops operating and the I/O data changes
to the safe states.
Name
None
Prevention
If cycling the power supply re-
stores normal operation, there
may be excessive noise near the
Unit. Implement noise counter-
measures.
Continuously