Connection status
General
Additional
Status
Status
(hex)
(hex)
OMRON error code
01
0810
01
0811
15-4-3
CIP Safety Connection Status Codes and Troubleshooting
This section explains how to identify and correct errors based on the connection status of CIP Safety
connection. If the CIP Safety Originator Connection Not Established error or the CIP Safety Target
Missing error occurs with the Safety CPU Unit, the connection status of the CIP Safety connection is
registered to the Attached information.
NX-series Safety Control Unit/Communication Control Unit User's Manual (Z395)
Source of error
Error code returned from target:
New data could not be obtained from the
Communication Control Unit when open-
ing connection. (The Unit will automati-
cally recover, and attempt to open the
connection again.)
Error code generated by originator:
New data could not be obtained from the
Communication Control Unit when open-
ing connection. (The Unit will automati-
cally recover, and attempt to open the
connection again.)
15 Troubleshooting
Handling
Configuration
Configuration
1
2
This error may
The meaning
occur if the
of this error
task period of
code is defined
the Communi-
by each ven-
cation Control
dor, so it de-
Unit was long
pends on the
when opening
target's specifi-
the connection
cations.
or some prob-
(Contact the
lem in the Con-
target device's
troller caused
manufacturer.)
the Controller
to stop.
If the task peri-
od was too
long, operation
recovers auto-
matically. If the
Controller has
stopped, identi-
fy the error
from the error
information in
the Communi-
cation Control
Unit.
This error may
The meaning
occur if the
of this error
task period of
code is defined
the Communi-
by each ven-
cation Control
dor, so it de-
Unit was long
pends on the
when opening
target's specifi-
the connection.
cations.
If the task peri-
(Contact the
od was too
target device's
long, operation
manufacturer.)
recovers auto-
matically.
Configuration
3
The meaning of
this error code
is defined by
each vendor,
so it depends
on the origina-
tor's specifica-
tions.
(Contact the
originator devi-
ce's manufac-
turer.)
15
The meaning of
this error code
is defined by
each vendor,
so it depends
on the origina-
tor's specifica-
tions.
(Contact the
originator devi-
ce's manufac-
turer.)
15-253
Need help?
Do you have a question about the sysmac NX Series and is the answer not in the manual?