SNMP/Web Card SC20G2
Operation Manual
Detailed setting
This document contains the information you need for using safely SNMP / Web card. Please read carefully
before installation and use.
Please keep it at hand carefully so that you can refer to it at any time, when this book is required.
The copyright of this book belongs to OMRON SOCIAL SOLUTIONS Co.,Ltd.To copy, reproduce and reprint
the contents partially oron the whole without notice to our company is refused firmly.
The contents of this document are subject to change without notice
About a picture, it may differ from the newest thing in part.
Windows and other names are the registered trademarks of U.S. Microsoft Corporation in the U.S. and
other countries.
Each other company names and each company product name are the trademarks or registered trademarks of each
company.
©OMRON SOCIAL SOLUTIONS CO.,LTD. 2014-2019. All Rights Reserved.
.

Advertisement

Table of Contents
loading

Summary of Contents for Omron SC20G2

  • Page 1 Please keep it at hand carefully so that you can refer to it at any time, when this book is required.  The copyright of this book belongs to OMRON SOCIAL SOLUTIONS Co.,Ltd.To copy, reproduce and reprint the contents partially oron the whole without notice to our company is refused firmly.
  • Page 2 Introduction Thank you for purchasing the OMRON SNMP/Web card lately ■ Corresponding model • This product is equipment which makes network connection possible by inserting in the slot of the OMRON uninterruptible power supply (UPS). ■ Functional feature • By inserting this product in an uninterruptible power supply (UPS), status acquisition from an uninterruptible power supply (UPS) and command issue to an uninterruptible power supply (UPS) are enabled.
  • Page 3: Table Of Contents

    Details of a UPS data log screen ....................82 Details of a UPS extended history log screen ................83 Setup of security ..........................84 Reference data ............................. 85 Specification ........................... 85 Upgrade of a firmware file ......................87 Configuration file read-out, edit, and writing of SC20G2 ..............90...
  • Page 4: Management By A Web Browser

    1. Management by a web browser 1.1. How to use the setting screen  Display procedure of setting screen Please start a web browser. Please input the IP address of a SNMP/Web card into an address bar. (Example: When an IP address is 192.168.2.150) About the setting method of the IP address of a SNMP/Web card, Please refer to "3.3 Network Configuration Method 2 :via Telnet "...
  • Page 5: Ups Monitoring] Menu

    1.2. [UPS Monitoring] Menu ・ The information about an uninterruptible power supply (UPS) is displayed. ・ The user can browse all those sub menus by read-only.  [Main Page] Menu ・ The basic operating state of the present uninterruptible power supply (UPS) is displayed by list.
  • Page 6 (UPS). UPS Temperature (℃) Displays the temperature of internal uninterruptible power supply (UPS). UPS Manufacture "OMRON" is displayed. Outlet A/B/C(Control)(sec) Display the used time of each output of the uninterruptible power supply (UPS). Input Frequency The present input frequency is displayed.
  • Page 7 12. UPS latest abnormality Last abnormality of UPS and time are displayed. 13. ACK Recovery notice of UPS last abnormality is issued by SNMP, Syslog, Mail. 14. UPS Next Off Time The schedule of the next uninterruptible power supply (UPS) power supply Off by schedule operation setup is displayed.
  • Page 8  [Parameters] Menu ・ Each state of the input power, output power and a battery of the present uninterruptible power supply (UPS) is displayed. ・ This page is automatically updated in [Page Refresh Rate (Sec)] time which can be set up at [SNMP/Web card management].
  • Page 9 The detail description of a screen [Output Parameters] Output Source The source of output power is displayed in the following state. [on line], [bypass], [battery],[no output] Output Frequency The present output frequency is displayed. Output Voltage The present output voltage is displayed. Output Load The connected-load capacity of the present uninterruptible power supply (UPS) is displayed by “%”.
  • Page 10  [UPS Outlet Information] Menu ・ The time chart to the uninterruptible power supply (UPS) shutdown set up by a shutdown setup and an uninterruptible power supply (UPS) outlet control function can be displayed according to an each outlet. ・ Overall operation of each outlet is checked with this chart. The detail description of a screen UPS Outlet Information The time chart according to outlet is...
  • Page 11  [Alarm Table] Menu ・ The state of alarm (buzzer) is displayed. ・ This page is automatically updated in [Page Refresh Rate] time which can be set up by a [SNMP/Web card configuration]. The detail description of a screen Number of Active Alarms The number of factors with which the present alarm is sounded is displayed.
  • Page 12  [Client Table] Menu ・ The information about the client and server on the network where automatic shutdown software is operating is displayed by list ・ A client is the computer which the shutdown agent is operating and is registered on the SNMP/Web card.
  • Page 13  [Netsearch] Menu ・ The PowerAct Pro agent on a network and a list of a SNMP/Web card are displayed. The detail description of a screen Master / Slave Group Master: The computer name which has installed SC20G22 or the master agent of PowerActPro is displayed.
  • Page 14: Ups Management] Menu

    1.3. [UPS Management] Menu ・ The controllable parameter information on an uninterruptible power supply (UPS) that the SNMP/Web card was inserted is displayed and set up. ・ The user can browse all those sub menus by read-only. ・ Read-write access is granted only to the system administrator. ...
  • Page 15 The detail description of a screen Input Voltage It is rated input voltage. Input Frequency It is rated input frequency. Output Voltage It is rated output voltage. Output Frequency It is rated output frequency. Output VA It is maximum output capacity (VA display). Over Temperature Set Point It is a maximum of the operative temperature of an uninterruptible power supply (UPS).
  • Page 16  [UPS Control] Menu ・ The immediate stop and reboot of an uninterruptible power supply (UPS) can be performed. ・ Some items can browsed by the access authority holder which can be read and written. Before login After login...
  • Page 17 The detail description of a screen Shutdown Immediately Immediate halt of an uninterruptible power supply (UPS) is performed. After clicking execute, UPS will stop after [UPS shutdown delay time] that appears at the bottom. The client shuts down immediately. Restart UPS An uninterruptible power supply (UPS) is rebooted.
  • Page 18  [UPS Test] Menu ・ A battery test and a function test are set up. ・ A short-time (about 10 seconds) simple battery test is included in a function test. ・ Some items can browsed by the access authority holder which can be read and written. Before login After login...
  • Page 19 The detail description of a screen [Battery Auto Test] Battery Auto Test Enable/disable of the automatic battery test of once every four weeks is set. Battery test is not done if it is disabled. Last Test Start Time It is the implementation date and time of the last battery test. Last Test Result It is the last battery test result.
  • Page 20  [UPS Test Schedule] Menu ・ The schedule for a test is displayed and set up. Before login After login...
  • Page 21 The detail description of a screen 1. Test Day Please set up a test execution day in a week. 2. Test Time Please set the test execution time. 3. Test Action Please specifies one of the following whether you carry out the self-test.
  • Page 22  [Shutdown Setting] Menu ・ The parameter at the time of performing the shutdown of a computer and a stop of an uninterruptible power supply (UPS) is set. Before login After login...
  • Page 23 ・ [Shutdown Event] The classification of an event is displayed. The detail description of a [Shutdown Event] AC Failed They are the abnormalities of the input power source represented by power failure. Battery Low It is the charge capacity decreasing of the battery. UPS Overload The capacity of connection apparatus exceeds the connection capacity maximum of a [UPS management] - [UPS...
  • Page 24 ・ [AC Restore/ AC Reboot] It reboots, when a power supply is restored, after the input power source of an uninterruptible power supply will be failed and it will stop, if set up enabled. When you hold a power supply OFF state then, please set up invalid. It may be unable to change depending on a model.
  • Page 25  [UPS Information] Menu ・ The information on an uninterruptible power supply (UPS) is displayed. The detail description of a screen 1. UPS Model It is the model of an uninterruptible power supply (UPS). 2. UPS Serial Number It is the SN of an uninterruptible power supply (UPS). 3.
  • Page 26  [UPS Remote Shutdown] Menu ・ The remote shutdown with multiple uninterruptible power supplies (UPS) is set up. It is used when backing up an uninterruptible power supply (UPS) and storage with a respectively different uninterruptible power supply (UPS). Before login After login...
  • Page 27 The detail description of a screen UPS-UPS Shutdown The enable/disable of an uninterruptible power supply (UPS) remote shutdown is set up. Work as master/slave UPS It specifies that which is used for this UPS between the master(UPS) or the slave(UPS). A master is only one set although it is possible to cooperate as one group and to operate two or more sets (UPS) of uninterruptible power supplies.
  • Page 28  [Weekly Schedule] Menu ・ A schedule setup in a week unit is performed. ・ Please determine operation on a [UPS management]-[shutdown setting] screen after a setup by this page. ・ When set up correctly, it is displayed on [UPS monitor]-[UPS main page] as a UPS next Off/On time.
  • Page 29 The detail description of a screen Shutdown day The day which halts an uninterruptible power supply (UPS) is set up per day of the week. Shutdown Time The time which halts an uninterruptible power supply (UPS) is set Restart Day The day which starts an uninterruptible power supply (UPS) is set up per day of the week.
  • Page 30  [Special Day Schedule] Menu ・ A schedule setup of a special day is performed. ・ Please determine operation on a [UPS management]-[shutdown setting] screen after a setup by this page. Before login After login...
  • Page 31 The detail description of a screen Shutdown day The day which halts an uninterruptible power supply (UPS) is set Shutdown Time The time which halts an uninterruptible power supply (UPS) is set Restart Day The day which starts an uninterruptible power supply (UPS) is set Restart Time The time which starts an uninterruptible power supply (UPS) is set...
  • Page 32: Snmp/Web Card Management] Menu

    1.4. [SNMP/Web Card Management] Menu ・ The information about the control parameter of a SNMP/Web card is displayed and set ・ Read-write access is granted only to the system administrator.  [Date and Time] Menu ・ The system time of a SNMP/Web card is displayed and set up. Before login After login...
  • Page 33 The detail description of a screen SNMP/Web Card System Date The system day of a SNMP/Web card is displayed. Changes can be set by way of lower. SNMP/Web Card System Time The system time of a SNMP/Web card is displayed. Changes can be set by way of lower.
  • Page 34  [SNMP/Web Card Configuration] Menu ・ The network parameter of a SNMP/Web card is displayed and set. Before login After login...
  • Page 35 The detail description of a screen SNMP/Web Card MAC Address The Mac address of a SNMP/Web card is displayed and set up. SNMP/Web Card IP Address The IP address of a SNMP/Web card is displayed and set up. (Input example: 192.168.2.150) SNMP/Web Card Gateway Address A gateway address is displayed and set up.
  • Page 36 12. Page Refresh Rate It will display and set the update time of the [Uninterruptible power supply (UPS) operating state list], [battery parameters], [input parameter], [output parameter], [alarm table], [Client Table] page. 13. BootP/DHCP Status It displays and sets up the enable/disable of the BootP/DHCP protocol which acquires an IP address.
  • Page 37  [SNMP/Web Card Control] Menu ・ Restart (reboot) of a SNMP/Web card and reset of an internal parameter can be performed. Before login After login...
  • Page 38 The detail description of a screen SNMP/Web Card Reset to Default Please choose when you reset the parameter of a SNMP/Web card to the initial value at the time of factory shipments. Restart SNMP/Web Card Please choose, when you restart a SNMP/Web card. Same Setting With Please set up the IP address of equipment which refers to the parameter of a SNMP/Web card.
  • Page 39  [Syslog Configuration] Menu ・ A Syslog function is displayed and set up. Before login After login...
  • Page 40 The detail description of a screen Syslog Enable/disable of a Syslog function are displayed and set up. Facility Facility of a Syslog function is displayed and set up. Syslog server The IP address of a Syslog server is displayed and set up. Map to Syslog’s Severity The information level at the time of sending out to a Syslog server about information level"Severe"and "Warning"...
  • Page 41  [Port Number Configuration] Menu ・ The port number of SNMP, HTTP, and Telnet is displayed and set up. Before login After login...
  • Page 42  [SNMP/Web Access Control] Menu ・ The IP address of NMS(computer) in which the read/write by SNMP/HTTP to a SNMP/Web card is enable is displayed and set up. Before login After login...
  • Page 43 The detail description of a screen NMS(NMS IP Address) The IP address of NMS is displayed and set up. It means not being set up in the case of 0.0.0.0. (Example: When 192.168.7.255 is set up, it means that the ranges from 192.168.7.0 to 192.168.7.255 of IP address were set Community The community of the set-up IP address is set up.
  • Page 44  [SNMP V3 Access Control] Menu ・ A setup at the time of communicating using SNMP V3 is performed to SC20G22. Before login After login...
  • Page 45 The detail description of a screen User Name The user name set up by the SNMP manager is inputted. It may be unnecessary by the security level to set up. Password The password set up by the SNMP manager is entered. It may be unnecessary by the security level to set up.
  • Page 46  [SNMP TRAP Receivers] Menu ・ The addressee of an SNMP trap is displayed and set up. Before login After login...
  • Page 47 The detail description of a screen NMS(NMS IP Address) It is an IP address of NMS used as the trap receiver's address. Community String It is a community. It can set up by a maximum of 19 characters. Trap Type It is a trap type which transmits.
  • Page 48 ・ The apparatus connected to UPS is registered, and it supervises by Ping to the IP address of apparatus, and performs a setup which controls shutdown operation of SC20G2 according to the success or failure of Ping. Before login After login...
  • Page 49 The detail description of a screen IP Address The IP address of the apparatus linked to UPS is inputted. Load Device The arbitrary character strings which identify and explain the apparatus linked to UPS are inputted. Device Shutdown Action When an error occurs in the response of Ping, it is set up individually whether script shutdown operation is performed to apparatus.
  • Page 50  [WakeOnLAN Targets] Menu ・ The MAC Address which transmits a WakeOnLAN packet is registered. It is used when rebooting two or more client PCs simultaneously at the time of an uninterruptible power supply (UPS) reboot. Before login After login...
  • Page 51 The detail description of a screen Repeating Times The sending number of a WakeOnLAN packet is set up. Interval Timer (Sec) The sending interval of a WakeOnLAN packet is set up. WakeOnLAN Numbers The number of the addressees of a WakeOnLAN packet is set up. MAC Address The addressee MAC Address of a WakeOnLAN packet is set up.
  • Page 52  [Script Shutdown] Menu ・ Set the shutdown operation which does not depend on the presence of automatic shutdown software by sending the script to the devices connected to the UPS. Before login After login...
  • Page 53 8. Wait time for run script (Sec) It delays the start time of script shutdown. 9. Select Script Number The script performed when SC20G2 starts shutdown operation is specified. A script is set up by the following clause "a script setup."...
  • Page 54  [Script Setting] Menu ・ The script which transmits to the apparatus connected to UPS is set up. Before login After login...
  • Page 55 The detail description of a screen 1. Script Name It set in any meaningful name to script, such as the target OS. 2. Script form A script to execute is described. 3. Set Value Descriptive content is saved by pressing the [Set Value] button. Please refer to the item of "Ping monitor setting"...
  • Page 56 [Script 5 : AVAYA Server] [Script 6 : Netapp] rcv=login: rcv=login: snd=$u1 snd=$u1 rcv=Password: rcv=Password: snd=$p1 snd=$p1 rcv=root logged in rcv=Enter your terminal type snd=<CR> snd=<CR> rcv=> rcv=> snd=halt snd=stop -h -f [Script 7 : FortiNet] [Script 8 : Symantec] rcv=login: rcv=login: snd=$u1...
  • Page 57 [About description of a script] 1. Each line of a script should describe "rcv=" or "snd=" at the head. 2. Each set of a script contains one "rcv=" and one "snd=", respectively. 3. Please use one line for every command. 4.
  • Page 58  [User Limited Function] Menu ・ The access restriction to the function to each user is set up. Before login After login...
  • Page 59 The detail description of a screen Admin User Name It is arbitrary and sets up an administrator's ID. (Factory default: "OMRON") Admin Password It is arbitrary and sets up an administrator's password. (Factory default: "admin") Limit User Name It is arbitrary and sets up ID of the user who wants to restrict a function.
  • Page 60  [CO2 Setting] Menu ・ The result of having computed at estimate the carbon-dioxide emissions of the apparatus (whole) connected to the uninterruptible power supply (UPS) is displayed. Before login After login...
  • Page 61 The detail description of a screen CO2 Discharge Coefficient It is arbitrary and sets up the discharge coefficient of CO2.(At the time of factory shipments: Initial value 0.000555 provided in the Ministry of Economy, Trade and Industry and an environmental ministerial ordinance third number) Data acquisition will be started, if the acquisition period of a log is set up and an execution button is pushed.
  • Page 62  [Email Notification] Menu ・ The notice of E-Mail of an uninterruptible power supply (UPS) state is set up. Before login After login...
  • Page 63 The detail description of a screen Mail Server The host name or IP address of an SMTP server is displayed and set up. When a host name is inputted, it is necessary to also input the DNS address of the lower. User Account The user account of a mail server is displayed and set up.
  • Page 64  [External Links] Menu ・ The link to the external is displayed and set up. ・ A maximum of four kinds of external link setup can be performed. ・ By putting an external Web page and link, a related Web page can be browsed easily. For example, you can easily access to the Web page in which technical support information is described or Web page of other uninterruptible power supply(UPS) in which the SNMP / Web card is inserted.
  • Page 65 The detail description of a screen Screen Text A name given in this column is displayed under the link on the left- hand side of a screen. Link Address URL of a link place is displayed and set up. Status Enable/Disable of a link display is set up.
  • Page 66: Ups History] Menu

    1.5. [UPS History] Menu ・ It displays according to the type of a [UPS history log], a [UPS extended log], a [UPS event log], a [SNMP/Web card event log], and a [UPS info log]. ・ By referring to these logs, the detection and diagnosis of a trouble relevant to a SNMP/Web card can be performed.
  • Page 67  [Clear & Save Log Data] Menu ・ Download and elimination of data are possible. ・ The log file of a SNMP/Web card can be saved by CSV format from this menu screen. The detail description of a screen Clear Log Data When an administrator eliminates specific log data, please click [clear] after putting a check beside object data.
  • Page 68: Power Management Ups

    2. Power management UPS 2.1 clauses explain the power supply state of a SNMP/Web card and 2.2 clauses or later explain power supply management of an uninterruptible power supply (UPS). 2.1. Power supply state of a SNMP/Web card According to the state of AC input to an uninterruptible power supply (UPS) and an uninterruptible power supply (UPS), etc., the power of a SNMP/Web card becomes as follows.
  • Page 69: Shutdown Immediately

    2.2. Shutdown Immediately  Setup Steps Please access the Web page of a SNMP/Web card and choose the [UPS management] - [UPS control] from an initial screen. Next, click [Become Administrator] and enter a user/password as an administrator. Next, please choose the radial button on the right of a [Shutdown Immediatly].Then, please click [execute].
  • Page 70  The example of a time chart Here, the case where the following conditions are set up is illustrated. Setting conditions Waiting time to a UPS stop (Sec) : 180(Initial value) Execution time of immediate shutdown : 22:20:00 The setting conditions of a client computer Time required for the end of application software :30 sec( Initial value...
  • Page 71: Ups Restart

    2.3. UPS Restart  Setup Steps Please access the Web page of a SNMP/Web card and choose the [UPS management] - [UPS control] from an initial screen. Next, click [Become Administrator] and enter a user/password as an administrator. Next, please choose the radial button on the right of a [Restart UPS].Then, please click [execute].
  • Page 72  The example of a time chart Here, the case where the following conditions are set up is illustrated. Setting conditions :180( Waiting time to a UPS stop (Sec) Initial value Delay time for UPS reboot(Min) :60 Reboot execution time :22:20:00 The setting conditions of a client computer Time required for the end of application software :30 sec(...
  • Page 73: The Shutdown At The Time Of An Abnormal Condition

    2.4. The shutdown at the time of an abnormal condition ・ The SNMP/Web card assumes four kinds of abnormal conditions, "AC failed", a "battery low", "UPS overload", and a "UPS Over temperature."  Setup Steps Please access the Web page of a SNMP/Web card and choose the [UPS management] - [Shutdown setting] from an initial screen.
  • Page 74  The example of a time chart [Example 1] Here, the case where the following conditions are set up is illustrated. Setting conditions Operation :client shutdown / UPS stop Waiting time (Min) :10( Initial value 1st warning (Sec) :30( Initial value Warning period (Sec) :30( Initial value...
  • Page 75: Schedule Shutdown

    2.5. Schedule shutdown  The kind of schedule shutdown The schedule shutdown which can be set as a SNMP/Web card is two kinds, "a schedule/weekly" and "a schedule/special day."  Before setting up Please check that the date and time of a SNMP/Web card are set up correctly. ...
  • Page 76 After [Set Value] and choose the [UPS management] - [Shutdown setting] from an initial screen. Please choose [client shutdown / UPS turn off] from a column [Shutdown actions], and set up various time Next click [Set Value] Button. The setting method of a schedule/special day is the same as that of a schedule/weekly.
  • Page 77  The example of a time chart [Example 1] Here, the case where the following conditions. Setting conditions Operation :client shutdown / UPS stop Waiting time (Min) :10( Initial value 1st warning (Sec) :30( Initial value Warning period (Sec) :30( Initial value (Sec) :180(...
  • Page 78: Setting Of Remote Shutdown

    2.6. Setting of remote shutdown It is possible to be shut down multiple uninterruptible power supply(UPS) in cooperative using the SNMP / Web card. When carrying out cooperative operation, one set becomes a master uninterruptible power supply (UPS), and others become a slave uninterruptible power supply (UPS).
  • Page 79  Setup steps The Web page of [UPS management]-[shutdown] on the master uninterruptible power supply (UPS) side is accessed, and a shutdown is set up according to the The Web page of [UPS management]-[UPS remote shutdown] on the master uninterruptible power supply (UPS) side is accessed, and it sets up as follows. UPS remote shutdown: Enable Select Work as master UPS Event occurs on Master UPS: Notify All...
  • Page 80 The Web page of [UPS monitor]-[client table] on the master uninterruptible power supply (UPS) side is accessed, and it checks that the slave uninterruptible power supply (UPS) is registered as a client uninterruptible power supply (UPS).  A master uninterruptible power supply (UPS) sends a shutdown command to a slave uninterruptible power supply (UPS) also when six events of a shutdown setting page occur.
  • Page 81  The example of a time chart Setting conditions of Master UPS Operation :client shutdown / UPS stop AC fail delay time (Min) :10( Initial value 1st warning (Sec) :30( Initial value Warning period (Sec) :30( Initial value (Sec) :180( Waiting time to a UPS stop Initial value AC failure occurring time...
  • Page 82: Management By Snmp

    3. Management by SNMP 3.1. Access control of a SNMP/Web card When you use a SNMP/Web card in the SNMP environment, please perform appropriately the IP address of a SNMP/Web card, and a setup of a gateway beforehand. It is recommendation about performing access control, in order to raise the security level of a SNMP/Web card.
  • Page 83: The Monitor Of The Log By A Java Applet

    4. The monitor of the log by a JAVA applet 4.1. Feature ・ The SNMP/Web card is equipped with GUI (graphical user interface) which moves by a JAVA applet. By GUI, the log of the uninterruptible power supply (UPS) on a network can be monitored in real time.
  • Page 84: Details Of A Ups Data Log Screen

    4.3. Details of a UPS data log screen If [Log] at the upper right of a screen is clicked by the homepage of a SNMP/Web card, an uninterruptible power supply (UPS) data log will be displayed on another window. In order to set up a display / un-displaying of a parameter, use the check box beside a parameter name.
  • Page 85: Details Of A Ups Extended History Log Screen

    4.4. Details of a UPS extended history log screen 1 If [Elog] at the upper right of a screen is clicked by the homepage of a SNMP/Web card, an uninterruptible power supply (UPS) extension data log will be displayed on another window. In order to set up a display / un-displaying of a parameter, use the check box beside a parameter name.
  • Page 86: Setup Of Security

    It is possible to change a security level (permitted level of access to a card) by setup with this product. The initial value of a user name, a password, a community user name, and a password is as follows. User name:OMRON Password:admin The community of SNMP is as follows. Read:public Read / Write:admin Community of read / write and password are the same.
  • Page 87: Reference Data

    Network protocol UDP, Telnet, SNTP, SMTP, DHCP, BOOTP, IPv4 Other communication Asynchronous serial interface (only setup) path UPS MIB(RFC1628) Supported MIB OMRON MIB Operating temperature 0~40℃ Operating humidity 10~80% BN50T, BN75T, BN100T, BN150T, BN220T, BN300T BN50S, BN75S, BN100S, BN150S, BN220S, BN300S...
  • Page 88 Switch part The position of DIP switch In the case of the bracket panel for BN-XR The operating state of a DIP switch operating state Unused Unused Unused Operation mode Port Green Yellow Operating state Blink (1 sec) 100Mbps Ethernet traffic Blink (1 sec) 10Mbps Ethernet traffic Ethernet cutting...
  • Page 89: Upgrade Of A Firmware File

    6.2. Upgrade of a firmware file When the firmware file of SC20G2 is updated, upgrade can be performed in the following procedures.  Work procedure The web browser of the Windows computer on the same network as SC20G2 is started, and the IP address assigned to SC20G2 is inputted into an address bar following "http://".
  • Page 90 Please choose "SNMP/Web card management" from the upper menu. Then, from a left menu, please choose a "SNMP/Web card configuration" and check that the item of "network upgrade" is "enable".
  • Page 91 Please confirm login ID (default: OMRON) and the password (default: admin) of SC20G2. Please put the SC20G2 firmware file used for update on the arbitrary places of a computer. Then, please insert enclosed CD-ROM in a computer and run "upgrade.exe" in a "SC20G2_Firmware_Upgrade"...
  • Page 92: Configuration File Read-Out, Edit, And Writing Of Sc20G2

    6.3. Configuration file read-out, edit, and writing of SC20G2 Using upgrade software, the configuration file of SC20G2 can be read, edit can be added, and a setup can be written in SC20G2 (SC20G2 which read a setup is included) on a network.  Work procedure Please insert enclosed CD-ROM in a computer and run "upgrade.exe"...
  • Page 93 Please click the "Save" button, if change is completed. A configuration file is updated. Next, please choose from a list SC20G2 on which a setup is reflected, and click the "Open" button like the time of firmware upgrade. If the dialog which opens a file is displayed, the pull down menu written to be "Binary Files (*.
  • Page 94 < The network adapter setting method for enabling a WakeOnLAN function > The property of a network adapter is opened from a device manager, and WakeOnLAN by Magic Packet is set up to enable. 1. Please open a [device manager] from [Control panel]> [System and Security]>[System]. 2.
  • Page 95 Please use a "UPS reboot" function to perform stop and starting of UPS. ・ Please check our homepage (https://www.oss.omron.co.jp/ups/) for the newest product information. Each company name and each company product name are the trademarks or registered trademarks of each company.