9. INSPECTIONS
The inspection should be conducted once every 6 months to a year.
Any inspected items which do not satisfy the criteria shown below should be repaired.
Inspection
Item
Power
Measure the voltage at the power supply terminal. Within 21.6 to 26.4VDC
supply
Ambient
Check the ambient temperature.
Conditions
There should be no accumulation of dust.
Verify that the ABSOCODER sensor is securely
mounted.
Verify that the ABSOCODER sensor shaft is
securely coupled to the machine shaft.
Mount
Check for severed cables.
Conditions
Verify that the sensor cable connector is plugged
in all the way.
Verify that the I/O connector is plugged in all
the way.
Inspection Description
Criteria
ABSOCODER sensor:
Converter: 0 to +55°C
None
There should be no looseness.
There should be no looseness.
Cable should appear normal.
There should be no looseness.
There should be no looseness.
41
Remark
Tester
-20 to +120℃
Thermometer
Visual
Inspection