If the connection is successful, the connectors icon at the bottom of the screen will come
together and clock information from the data logger will be displayed in the Station Date/Time
field. If the connection fails, a Communications Failure message will be displayed.

12.2.2 Modules using a public static IP

12.2.2.1 Configure data logger

12.2.2.2 Set up LoggerNet
12.2.2.3 Test the connection
12.2.2.1 Configure data logger
 1. Connect the cellular antenna, if it is not already connected. When using a MIMO antenna
with multiple cellular connections, connect the primary cable to Cellular and the secondary
to Diversity. If the cables are not marked in this way, they can be connected to either
antenna port.
 2. Connect to your data logger by using Device Configuration Utility.
 3. On the PPP tab, set Config/Port Used to CS I/O SDC8 or RS-232, depending on how you
are connected to the data logger.
 4. (Optional) On the PPP tab, set User Name and Password if required by your cellular carrier
(usually outside of the United Sates).
 5. (Optional) If your cellular carrier requires user name and password authentication, on the
Settings Editor > Cellular tab, set PDP Authentication Type, PPP Authentication Username
and PPP Authentication Password.
 6. Verify the Modem Dial String setting is blank.