Cellpdpusername; Cellpwrduration - Campbell CR300 Series Product Manual

Compact datalogger
Hide thumbs Also See for CR300 Series:
Table of Contents

Advertisement

Where to find:
 
Settings Editor tab in Device Configuration Utility: Cellular > PDP Cell Authentication
l
Password

23.3.59.8 CellPDPUserName

Specifies the username used for PDP authentication. Often there is no username, and this field
can be left blank. If a Username is required, it will be provided by your cellular provider with the
APN.
 
String data type
l
Where to find:
 
Settings Editor tab in Device Configuration Utility: Cellular > PDP Cell Authentication
l
Username

23.3.59.9 CellPwrDuration

Specifies the interval, in minutes, over which the data logger will power its cellular interface. This
can be done to save on battery life or cellular charges. This is adjusted using three components:
 
Start (Power-On) Time: Specifies the time of day in terms of hours and minutes in which the
l
data logger will first enable the cellular interface. If left at the default value of Always On,
the data logger will power the cellular interface at all times.
 
On Duration: Specifies the interval, in minutes, to power the data logger cellular interface
l
for the first time of any day as well as for any repeat cycles (if applicable).
 
Repeat Cycle: Specifies the interval after the first time that the data logger powers on its
l
cellular interface, that the data logger will power its cellular interface at subsequent times
throughout the day.
For example, setting a Start Time of 08:00, with an On Duration of 15 minutes, and a Repeat Cycle
of Every Hour, will result in the cellular module being powered on at 8:00AM for 15 minutes every
hour until midnight.
 
Long data type
l
Where to find:
 
Settings Editor tab in Device Configuration Utility: Cellular > On duration
l
23. Information tables and settings (advanced)     225