Lenovo ThinkSystem SD650-N Manual page 67

Neptune dwc tray and neptune dwc enclosure
Table of Contents

Advertisement

2. If no problem is observed on the DIMM connectors or the problem persists, replace the DIMM
identified by LightPath and/or event log entry.
3. If problem recurs on the same DIMM connector, replace the other DIMMs on the same memory
channel.
4. Check Lenovo support site for an applicable service bulletin or firmware update that applies to this
memory error.
5. If problem recurs on the same DIMM connector, inspect connector for damage. If damage found or
problem persists, collect Service Data log.
6. Contact Lenovo Support.
• FQXSPMA0012M: An Over-Temperature Condition has been detected on the
[PhysicalMemoryElementName] on Subsystem [MemoryElementName].
This message is for the use case when an implementation has detected an Over Temperature Condition
for Memory that has been Detected.
Severity: Error
Serviceable: Yes
Automatically notify Support: No
Alert Category: Critical - Temperature
SNMP Trap ID: 0
CIM Prefix: PLAT CIM ID: 0146
User Action:
Complete the following steps:
1. Check the event log of system management module and XClarity Controller for any cooling related
issue.
2. Make sure CDU supply water temperature and flow rate per tray is within operating specifications.
3. Make sure waterloop assembly and maifold are installed correctly.
4. Make sure that the room temperature is within operating specifications.
5. If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
• FQXSPMA0022I: Post Package Repair Success for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName].
This message is for the use case when an implementation has detected that Memory double chip sparing
has been initiated.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: System - Other
SNMP Trap ID: 22
CIM Prefix: PLAT CIM ID: 0140
User Action:
Information only; no action is required.
• FQXSPMA2007I: Scrub Failure for [PhysicalMemoryElementName] on Subsystem
[MemoryElementName] has recovered.
This message is for the use case when an implementation has detected a Memory Scrub failure recovery.
Severity: Info
Serviceable: No
.
Chapter 2
XClarity Controller events
63