Electrical Installation - Burkert 8695 Operating Instructions Manual

Hide thumbs Also See for 8695:
Table of Contents

Advertisement

Type 8695
Electrical installation 24 V DC
9.2

Electrical installation

Configuration circular plug (M12 x 1, 8-pole):
Figure 21:
Circular plug M12 x 1, 8-pole
Pin
Wire color
Designation
3)
1
white
limit switch top
2
brown
limit switch bottom
3
green
Supply voltage
4
yellow
Supply voltage +
5
grey
Valve control unit +
6
pink
Valve control unit -
7
-
8
-
Table 3:
Connection with circular plug-in connector
Connect the control head according to the table.
When the supply voltage is applied, the control head is operating.
To read in the end positions of the valve, start the teach function (see "9.3 Teach function (calibrating the end
position)").
The indicated colors refer to the connecting cable available as an accessory (919061).
3)
5
6
4
7
3
8
2
1
Configuration
IN 1 (=Top)
IN 2 (=Bot)
GND
24 V DC
Valve +
Valve -
not used
not used
External circuit / signal level
+ 24 V
1
IN 1
{
IN 2
2
100K
GND
3
GND
4
24 V
5
24 V
6
GND
english