As-Interface Installation; As-Interface Connection; Technical Data For As-Interface Pcbs; Programming Data - Burkert 8695 Operating Instructions Manual

Hide thumbs Also See for 8695:
Table of Contents

Advertisement

Type 8695

AS-Interface installation

10
AS-INTERFACE INSTALLATION
10.1

AS-Interface connection

AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).
Bus line
Unshielded two-wire line (AS-Interface line as AS-Interface cable harness) along which both information (data) and
energy (supply voltage for the actuators and sensors) are transmitted.
Network topology
Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details are described in the
AS-Interface specification (A/B slave model conforms to the version 3.0 specification).
10.2

Technical data for AS-Interface PCBs

Supply:
via AS-Interface (24 V + 20 % / -10 %)
Outputs:
1 Valve Y1, max. 1 W, Power reduction after approx. 100 ms
with integrated Watch-Dog function
Certification: Certificate no. 87301 after version 3.0
10.3

Programming data

I/O configuration
ID code
Extended ID code 1
Extended ID code 2
Profile
Table 6:
Programming data
Bit configuration
Data bit
D3
0 Top not reached
Input
1 Top reached
Output
Parameter bit
P3
Output
not used
Table 7:
Bit configuration
B hex
A hex (see below for bit configuration)
7 hex
E hex
S-B.A.E
D2
D1
0 Bot not reached
1 Bot reached
P2
not used
D0
0 Pilot valve
not used
1 Pilot valve
P1
P0
"0" START Teach function
not used
"1" STOP Teach function
english
OFF
ON
39