Electrical Data; Electrical Data Without Bus Control 24 V Dc; Electrical Data With As-Interface Bus Control; Electrical Data With Devicenet Bus Control - Burkert 8695 Operating Instructions Manual

Hide thumbs Also See for 8695:
Table of Contents

Advertisement

6.8

Electrical data

WARNING!
Only circuits with limited power may be used for UL approved components according to "NEC Class 2".
6.8.1

Electrical data without bus control 24 V DC

Protection class
Connections
Pilot valve
Operating voltage
Power input
Output
Display
6.8.2

Electrical data with AS-Interface bus control

Protection class
Connections
Profile
Operating voltage
Outputs
Max. switching capacity
Watchdog function
Max. power consumption
Power consumption input during
normal operation
(after current reduction;
valve + 1 end position reached)
6.8.3

Electrical data with DeviceNet bus control

Protection class
Connections
Operating voltage
Max. power consumption
Output
Pull-in current current
Holding current
16
3 as per DIN EN 61140 (VDE 0140-1)
Circular plug-in connector (M12 x 1, 8-pole)
24 V DC ± 10% - max. residual ripple 10 %
max. 1 W
max. 100 mA per output
max. 20 mA per illustrated illuminated display (LED)
3 as per DIN EN 61140 (VDE 0140-1)
Circular plug-in connector (M12 x 1, 4-pole)
S-B.A.E. (A/B slave, max. 62 slaves/master)
29.5 V – 31.6 V DC (according to specification)
1 W via AS-Interface
integrated
120 mA
90 mA
3 as per DIN EN 61140 (VDE 0140-1)
Circular plug-in connector (M12 x 1, 5-pole)
11 V – 25 V
< 80 mA
≤ 50 mA
≤ 30 mA
english
Type 8695
Technical data

Advertisement

Table of Contents
loading