Data Formatting - ProMinent DULCOMETER Installation And Configuration Manual

Measuring and control unit aegis s for cooling water applications
Table of Contents

Advertisement

Modbus
Number
Name
register
of regis‐
ters
Contacts
46051
12
switch_DI1
46076
12
switch_DI2
46101
12
switch_DI3
46126
12
switch_DI4
46151
12
switch_DI5
46176
12
switch_DIS
Modbus
Number
Name
register
of regis‐
ters
Relays
46301
58
relay_PO1
46401
58
relay_FO1
46501
58
relay_FO2
46601
58
relay_FO3
46701
58
relay_FO4
46801
58
relay_RO1
Modbus
Number
Name
register
of regis‐
ters
Relays
47801
18
iout_AO1
47826
18
iout_AO2
11.2

Data Formatting

BOOL
Access
Format
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
Access
Format
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
r
STRUC
T
Access
Format
r
STRUC
T
r
STRUC
T
"bool" uses 1 register and can have two values 0 or 1.
Example:
Modbus Communication Register
Description
Contact status DI1
Contact status DI2
Contact status DI3
Contact status DI4
Contact status DI5
Contact status SI
Description
PO1 relay states and value
FO1 relay states and value
FO2 relay states and value
FO3 relay states and value
FO4 relay states and value
RO1 relay states and value
Description
States and value of the output 4...20mA
AO1
States and value of the output 4...20mA
AO2
85

Advertisement

Table of Contents
loading

Table of Contents