Assembly and Installation
Fig. 18: F04

4.8 Electronic relay outputs connections RO1

Fig. 19: R01
24
1.
Remove the protective sheath and strip wires on 7 mm.
2.
Pass the cable through a cable gland.
3.
Connect a cable on the midpoint COMMUN (42) of the ter‐
minal block.
4.
Connect the second cable on the WORK (41) of the terminal
block or on the REST (43) depending on the function to be
performed.
1.
Remove the protective sheath and strip wires on 7 mm.
2.
Pass the cable through a cable gland.
3.
Connect a cable on the midpoint COMMUN (48) of the ter‐
minal block.
4.
Connect the second cable on the WORK (47) of the terminal
block or on the REST (49) depending on the function to be
performed.
The electronic relay output is mainly dedicated to controlling the
dosing pumps in impulse mode. It can also serve as alarm relay or
for control of dosing pumps.
WARNING!
This relay is an electronic component that makes a
contact, it is used to drive pumps by their impulse
input or to control an external power relay. This
relay can switch a maximum voltage of 48 VAC
and a current of 50 mA.
1.
Remove the protective sheath and strip wires on 7 mm.
2.
Pass the cable through a cable gland.
A3765
A3766