Serial Input Si1; Self-Powered Relay Po1; Potential-Free Relays (Fo1 To Fo4) - ProMinent DULCOMETER Installation And Configuration Manual

Measuring and control unit aegis s for cooling water applications
Table of Contents

Advertisement

Assembly and Installation

4.5.5 Serial input SI1

Fig. 13: Serial input SI1

4.6 Self-powered relay PO1

Fig. 14: Self-powered relay PO1

4.7 Potential-free relays (FO1 to FO4)

22
Connection of a CTFS sensor on SI1:
1.
Remove the protective sheath.
2.
Strip the wires on 7 mm.
3.
Pass the cable through the cable gland.
4.
Connect the red power strand to SI1 + (9).
5.
Connect the black power strand to SI1 – (10).
6.
Connect the green contact strand to SI1 sw (11).
The self-powered PO1 power relay output (Primary supply voltage
= Voltage available on P3) can be used to control the bleed valve.
A3761.
1.
Strip the 3 wires of the power cable of the dosing device on 7
mm.
2.
Pass the 3-point cable through a cable gland.
3.
Connect the phase on L1 (50) and the neutral on N (51) of
the PO1 mains terminal block.
4.
Connect the earth on PE (52) of the PO1 mains terminal
block.
The potential-free relay outputs can be used for the control of
dosing pumps.
A3760
A3761