7.2.3 BIOCIDE B TIMERS

Biocide
60
Winter
Summer/
Winter
In this menu timers for biocide dosing are defined. The option are
similar to the menu BIOCIDE A TIMERS. BIO-INHIB-DISP SET‐
TINGS BIO-INHIB-DISP SETTINGS menu will allow you to adjust
the settings of the parameters of the Biocides, inhibitor and disper‐
sant.
Fig. 67: Overview biocide, inhibitor and dispersant settings
Pre-bleed
There are 2 possibilities for pre-bleed: The
duration or the percent of hysteresis. It
depends on the pre-bleed mode you have
chosen in the OUTPUT SETTINGS.
Possible adjustment from 0 to 1440 min.
Possible adjustment from 0 to 100 %.
Duration of the post
Enter the duration of the post bleed action
bleed action
value. Possible adjustment from 0 to 1440
min.
You have 8 timers (in white in
the "Winter" part) at your dis‐
posal.
These timers are valid
throughout the year (From Jan‐
uary to December).
You have 16 timers at your dis‐
posal.
The 8 timers of the "Summer"
part will be active for the
months of May, June, July,
August and September (In grey
part).
The 8 timers of the "Winter" part
will be active for the months of
January, February, March, April,
October, November and
December (In white part).