Replacing An Indicator - Huawei UPS5000-E-180 kVA User Manual

Hide thumbs Also See for UPS5000-E-180 kVA:
Table of Contents

Advertisement

UPS5000-E-180 kVA
User Manual (Integrated UPS, 30 kVA Power
Modules)
Step 5 Reinstall the protective panel.
----End

8.3 Replacing an Indicator

Prerequisites
Tools and Materials
Procedure
Step 1 Remove the indicator fuse from the fuse terminal block at the rear of the cabinet
to disconnect the circuit. For the MCCB input, the fuse is installed at No. 1 fuse
base.
Step 2 Remove the protective panel.
Figure 8-14 Removing the protective panel
Step 3 Remove the indicator fastener using an insulated Phillips torque screwdriver.
Step 4 Use a multimeter to measure the voltage of the faulty indicator. If no voltage is
detected, the indicator needs to be replaced.
Issue 05 (2024-01-30)
An indicator is faulty.
A spare indicator of the same model is available and functional.
Phillips insulated torque screwdriver
Key
Protective gloves
Multimeter
Step ladder
Spare indicator
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Parts Replacement