Gira 2100 Series Manual page 77

Continuous regulator / object regulator
Hide thumbs Also See for 2100 Series:
Table of Contents

Advertisement

Operation concept
Time between short- and
long-time operation base
Time between short- and
long-time operation
factor (4 ... 127)
07/17
Subject to change without notice
short - long - short
long - short
130 ms
260 ms
...
34 s
4 ... 127, 4
instabus KNX/EIB System
Sensor
Determines the telegram sequence following a
key-press.
Short – long – short:
Drücken
T1
Loslassen = STEP
STEP
MOVE
Pressing the key will transmit a STEP command
and time T1 ("time between short and long-time
operation") is started. If the key is released
within T1, no further telegram will be
transmitted. This STEP serves the purpose of
stopping a continuous move.
If the key is pressed longer than T1, a MOVE
command is automatically transmitted after T1
has elapsed and time T2 ("slat adjustment
time") is started. A STEP command will be
transmitted, if the key is released again within
T2. This function is used for the adjustment of
the slats. T2 should correspond to the time
needed for a slat rotation through 180°.
Long – Short:
Drücken
T1
Loslassen = STEP
MOVE
Pressing a key will transmit a MOVE command
and time T1 ("slat adjustment time") is started. A
STEP command will be transmitted, if the key is
released again within T1. This function is used
for the adjustment of the slats. T1 should
correspond to the time required for a 180°
rotation of the slats.
Time after which the function assigned to the
long key-press is executed.
Only if "Operation concept" = "Short – Long –
Short".
2100-xx/2101 xx Page 77/82
T2
Keine Aktionen
Keine Aktionen