Number of addresses (max):
Number of assignments (max):
Communication objects:
Pushbutton interface functions:
Function:
Binary input / switching (for all 4 binary inputs (X = 1 to 4)) disabling function enabled
Object-Nr.
Function
0-3
Switching object X.1
4-7
Switching object X.2
8-11
Disable switching object X.1
12-15 Disable switching object X.2
Function:
Binary input / dimming (for all 4 binary inputs (X = 1 to 4)) disabling function enabled
Object-Nr.
Function
0-3
Switching
4-7
dimming
8-11
Disabling
Function:
Binary input / blind/shutter (for all 4 binary inputs (X = 1 to 4)) disabling function enabled
Object-Nr.
Function
0-3
Short-time operation
4-7
Long-time operation
8-11
Disabling
Function:
Binary input / dimming value transmitter (for all 4 binary inputs (X = 1 to 4)) disabling function
enabled
Object-Nr.
Function
0-3
Value
8-11
Disabling
Function:
Binary input / light-scene extension (for all 4 binary inputs (X = 1 to 4)) disabling function
enabled
Object-Nr.
Function
0-3
Light-scene extension
8-11
Disabling
Function:
Binary input / brightness value transmitter (for all 4 binary inputs (X = 1 to 4)) disabling function
enabled
Object-Nr.
Function
0-3
Brightness value
8-11
Disabling
07/17
Subject to change without notice
120
120
59
Name
PBI input X
PBI input X
PBI input X
PBI input X
Name
PBI input X
PBI input X
PBI input X
Name
PBI input X
PBI input X
PBI input X
Name
PBI input X
PBI input X
Name
PBI input X
PBI input X
Name
PBI input X
PBI input X
instabus KNX/EIB System
Sensor
dynamic table handling
maximum length of table
DPT–ID
1.001
1.001
1.001
1.001
DPT–ID
1.001
3.007
1.001
DPT–ID
1.007
1.008
1.001
DPT–ID
5.001
1.001
DPT–ID
18.001
1.001
DPT–ID
9.004
1.001
Yes
No
120
Type
Flag
1 bit
C, T
1 bit
C, T
1 bit
C, W
1 bit
C, W
Type
Flag
1 bit
C, T
4 bit
C, T
1 bit
C, W
Type
Flag
1 bit
C, T
1 bit
C, T
1 bit
C, W
Type
Flag
1 byte
C, T
1 bit
C, W
Type
Flag
1 byte
C, T
1 bit
C, W
Type
Flag
2 bytes
C, T
1 bit
C, W
2100-xx/2101 xx Page 13/82