Continuous regulator / object regulator
Hide thumbs Also See for 2100 Series:
Table of Contents

Advertisement

Operating mode switch-over via value (1-byte)
Operating mode after reset
Only with operating mode switch-over via 1-bit objects:
Operating mode when all bit
objects = 0
(preferred state)
Setpoint values
Basic temperature after
reset (7 ... 4) * 1 °C
Basic temperature setpoint
change
Adopt basic temperature
setpoint permanently
Frost protection setpoint
temperature
(7...40) * 1 °C
Heat protection setpoint
temperature
(7...45) * 1 °C
07/17
Subject to change without notice
Via switching (4 x 1-bit)
Comfort mode
standby mode
Night mode
Frost /heat protection
Comfort mode
standby mode
Night mode
Frost /heat protection
last state before change to 0
7.0 °C ... + 40 °C, 21 °C
deactivated
permit via the bus
NO
YES
7 °C ... + 40 °C, 7 °C
7 °C ... + 45 °C, 35 °C
instabus KNX/EIB System
Sensor
The switch-over of the operating modes via the
bus takes place according to the KONNEX
specification via a 1-byte value object. In
addition, a higher-ranking forced-control object
is available for this setting.
The 'classic' switch-over of the operating modes
via the bus is via separate 1-bit objects.
Defines the operating mode which is set, for
instance after a reset caused by bus voltage
return or by new programming.
Defines the operating mode which is activated
when all 1-bit operating mode objects have
value "0".
Defines the basic setpoint value after the
initialization.
Determines whether an adjustment of the basic
temperature possible via the bus.
This parameter determines whether the basic
temperature value which has been adjusted via
the bus is to be permanently (setting "yes") or
only temporarily (setting "no") stored in memory.
When set to "yes" the changed basic value will
be retained even after a switch-over of the
operating mode and after a reset.
Only if "Basic temperature setpoint change" =
"permit via the bus"
Defines the setpoint temperature with activated
frost protection.
Only if "Control option" = "heating" or "heating
and cooling", if applicable, with additional stage
Defines the setpoint temperature with activated
heat protection.
Only if "Control option" = "cooling" or "heating
and cooling", if applicable, with additional stage.
2100-xx/2101 xx Page 67/82