Room temperature measurement
Temperature detection
Determination of measured
value from internal /
external ratio
Calibration of internal
sensor
(-128...127) * 0.1 K
Calibration of external
sensor
(-128...127) * 0.1 K
Interrogation interval for
external sensor
(0...255) * 1 min;
0 = inactive
Transmission when room
temperature changes by
(0..255) * 0,1 K;
0 = no automatic
transmission
Cyclical transmission of
room temperature
(0...255) * 1 min;
0 = inactive
Actuating variable and status output
07/17
Subject to change without notice
internal sensor
external sensor
internal and external sensor
10% to 90 %
20% to 80 %
30% to 70 %
40% to 60 %
50% to 50 %
60% to 40 %
70% to 30 %
80% to 20 %
90% to 10 %
-128 ... 127, 0
-128 ... 127, 0
0 ... 255, 0
0 ... 255, 3
0 to 255, 15
instabus KNX/EIB System
Sensor
Determines which sensor will be used for room
temperature measurement.
Internal sensor: built-in sensor of the controller
External sensor: an external sensor coupled via
the bus, e.g. for severe measuring conditions
(swimming pools or similar).
Internal and external sensor: Both sensors are
used, for example, in large rooms.
Determines the weighting of the measured
temperature value for the internal and external
sensors.
That results in an overall value which will be
used for the further evaluation of the room
temperature.
Only if "Temperature detection" = "internal and
external sensor"
Determines the value by which the internal
sensor's room temperature value is calibrated.
Only if "Temperature detection" = "internal
sensor" or "internal and external sensor".
Determines the value by which the external
sensor's room temperature value is calibrated.
Only if "Temperature detection" = "external
sensor" or "internal and external sensor".
Determines the interrogation interval for the
external sensor's temperature value .
0" = sensor transmits its temperature value
automatically.
Only if "Temperature detection" = "external
sensor" or "internal and external sensor".
Determines the size of the value change of the
room temperature after which the current values
are automatically transmitted to the bus via
"Actual temperature" object 23.
Determines whether or when the determined
room temperature is to be cyclically output via
"Actual temperature" object 23.
2100-xx/2101 xx Page 71/82