Setpoints For The "Heating" Control Option - Gira 2100 Series Manual

Continuous regulator / object regulator
Hide thumbs Also See for 2100 Series:
Table of Contents

Advertisement

2.4.1.1

Setpoints for the "heating" control option

The setpoint temperatures for comfort, standby and night mode exist for this control option. The frost protection
temperature can be preset. The following applies:
T
standby setpoint heating
The standby and night setpoint temperatures are derived from the comfort setpoint temperature (basic setpoint) in
line with the parameterized decrease-temperatures.
The frost protection is supposed to prevent the heating system from freezing. For this reason the frost protection
temperature should be set to a smaller value than the night temperature for heating (default: +7 °C). In principle,
however, it is possible to select frost protection temperature values between +7 °C and +40 °C.
The possible range of values for a setpoint temperature lies between + 7.0 °C and + 99.9 °C for "heating" and is
limited by the frost protection temperature in the lower range.
The stage offset parameterized in the ETS will be additionally considered in a two stage heating mode.
Additional stage comf. temp.
Additional stage standby temp.
Additional stage night temp.
T
comfort setpoint additional stage heating
T
comfort setpoint additional stage heating
07/17
Subject to change without notice
Temperature
Comfort
mode
Comfort temp.
= basic setpoint
Standby temperature
Night temp.
(Recommended setpoint temperatures)
≤ T
comfort setpoint heating
Basic stage comf. temp.
Basic stage standby temp.
Basic stage night temp.
≤ T
comfort setpoint basic stage heating
T
standby setpoint heating
≤ T
comfort setpoint basic stage heating
T
night setpoint value heating
Standby
Night
Frost/heat prot.
mode
mode
Standby
heating
Night
temp. decrease
heating
temp. decrease
or T
night setpoint heating
Temperature
Comfort
Standby
mode
mode
SW
SW: Step width parameterized in the ETS plug-in
/ T
standby setpoint additional stage heating
stage heating
≤ T
comfort setpoint heating
or
/ T
night setpoint additional stage heating
heating
≤ T
comfort setpoint heating
instabus KNX/EIB System
Sensor
mode
Frost protection
setpoint
≤ T
comfort setpoint heating
Night
Frost/heat prot.
mode
Standby
heating
Night
temp. decr.
heating
SW
temp. decrease
SW
Frost protection
≤ T
standby setpoint basic
≤ T
night setpoint basic stage
2100-xx/2101 xx Page 47/82