Continuous regulator / object regulator
Hide thumbs Also See for 2100 Series:
Table of Contents

Advertisement

instabus KNX/EIB System
Sensor
Automatic transmission if
value changes by...
(0...100) * 1 %; 0 = inactive
Cycle time of switching
variable
(1...255) * 1 min
Cycle time for automatic
transmission
(0...255) * 1 min;
0 = inactive
Output of actuating variable
heating
Output of actuating variable
basic stage heating
Output of actuating variable
additional stage heating
Output of actuating variable
cooling
72/82 Page 2100-xx/2101 xx
0 to 100, 3
1 to 255, 15
0 to 255, 10
inverted (closed when sourcing
current)
normal (opened when sourcing
current)
inverted (closed when sourcing
current)
normal (opened when sourcing
current)
inverted (closed when sourcing
current)
normal (opened when sourcing
current)
inverted (closed when sourcing
current)
normal (opened when sourcing
current)
Determines the size of the actuating variable
change that will cause the automatic
transmission of the continuous actuating
variables via the actuating variable objects.
Only if at least one type of control is
parameterized to "continuous PI control"!
Determines the cycle time for the pulse-width-
modulated actuating variable (PWM).
Only if at least one type of control is
parameterized to "switching PI control (PWM)".
Time interval for the cyclical transmission of the
actuating variable via the actuating variable
objects.
Only if at least one type of control is
parameterized to "continuous PI control" or
"switching 2-state control".
continuous: Act. var.= 100 % - normal act. var.
switching:
Act. var. = 1 - normal act. var.
normal actuating variable output heating
Only if "Control option" = "heating" or "heating
and cooling".
continuous: Act. var. = 100 % - normal act. var.
switching:
Act. var. = 1 - normal act. var.
normal actuating variable output basic stage
heating
Only if "control option= basic and additional
heating" or "basic/additional heating/cooling".
continuous: Act. var. = 100 % - normal act.var.
switching:
Act. var. = 1 - normal act. var.
normal actuating variable output additional
stage heating
Only if "Control option" = "basic and additional
heating" or "basic/additional heating/cooling".
continuous: Act. var. = 100 % - normal act. var.
switching:
Act. var. = 1 - normal act. var.
normal actuating variable output cooling
Only if "Control option" = "cooling" or "heating
and cooling".
07 /17
Subject to change without notice