Continuous regulator / object regulator
Hide thumbs Also See for 2100 Series:
Table of Contents

Advertisement

instabus KNX/EIB System
Sensor
Upper hysteresis of the 2-
state controller heating
(5 ... 127) * 0.1 K
Lower hysteresis of the 2-
state controller heating
(-128 ... –5) * 0.1 K
Type of cooling control
(if applicable, for basic and
additional stage)
Only with continuous or switching PI control:
Type of cooling
(if applicable, for basic and
additional stage)
Only with separate input of control parameter:
Proportional range cooling
(10 ... 127) * 0.1 K
Reset time cooling
(0 ... 255) * 1 min; 0 =
inactive
Only with switching 2-state control:
Upper hysteresis of the 2-
state controller cooling
(5 ... 127) * 0.1 K
Lower hysteresis of the 2-
state controller cooling
(-128 ... –5) * 0.1 K
66/82 Page 2100-xx/2101 xx
5...127, 5
-128...-5, -5
Continuous PI control
Switching PI control PWM)
Switching 2-point control
(ON/OFF)
Cooling ceiling (5 K / 240 min)
Fan convector (4 K / 90 min)
Split unit (4 K / 90 min)
Via control parameter
10...127, 50
0...255, 240
5...127, 5
-128...-5, -5
Definition of switch-on and switch-off
temperatures for heating.
Only if "type of heating control" = "2-state".
Definition of switch-on and switch-off
temperatures for heating.
Only if "type of heating control" = "2-state".
Selects a control algorithm (PI or 2-state) with
data format (1 byte or 1 bit) for the cooling
system.
Only if "Transmit actuating variables for heating
and cooling to shared object" = "no".
If "Transmit actuating variables for heating and
cooling to shared object" = "yes", the parameter
settings for "Type of heating control" will be
accepted.
Adapts the PI algorithm to different cooling
systems using experience values for the
proportional range and reset time control
parameters.
Separate input of control parameter.
Separate setting of the "proportional range"
control parameter.
Only if "Type of cooling" = "via control
parameter".
Separate setting of the "reset time" control
parameter.
Only if "Type of cooling" = "via control
parameter".
Defines the switch-on and switch-off
temperatures for cooling.
Only if "Type of cooling control" = "2-state".
Defines the switch-on and switch-off
temperatures for cooling
Only if "Type of cooling control" = "2-state".
07 /17
Subject to change without notice